LSRK045.T

POWR-GARD
®
Fuse Datasheet
© 2016 Littelfuse POWR-GARD
®
Products
Rev: 1-A-031716
littelfuse.com
1 of 3
CLASS RK1 – LLNRK • LLSRK • LLSRK_ID SERIES FUSES
250/600 Vac • Dual Element • Time-Delay •
1
/
10
-600 A
Description
RK1 fuses are extremely current-limiting fuses meaning they
greatly reduce or eliminate damage to circuits and equipment under
short-circuit conditions. Replacing existing Class H, K and RK5 fuses
with RK1 fuses is one of the easiest ways to immediately improve
the protection of plant workers and equipment.
Applications
All general purpose circuits
Motors
Transformers
Safety upgrades
Features/Benefits
POWR-PRO Performance
Indication available
Dual-element design
Extremely Current-Limiting
IEC Type 2 “No Damage” protection to IEC and NEMA
type motor starters
Indicating and DIN mount fuse holders available
Specifications
Voltage Ratings 600 Vac/300 Vdc (LLSRK/LLSRK_ID)
250 Vac/125 Vdc (LLNRK)
Interrupting Ratings AC: 200 kA rms symmetrical
300 kA rms symmetrical
(Littelfuse self-certified)
DC: 20 kA
Ampere Range 1/10 – 600 A
Approvals AC: Standard 248-12, Class RK1
UL Listed (File: E81895)
CSA Certified (File: LR29862)
DC: Littelfuse self-certified
Federal Specification WF-1814
(QPL- W-F-1814)
AMPERE RATINGS
1
/
10
1 2
8
/
10
6
1
/
4
25 80 250
15
/
100
1
1
/
8
3 7 30 90 300
2
/
10
1
1
/
4
3
2
/
10
8 35 100 350
1
/
4
1
4
/
10
3
1
/
2
9 40 110 400
3
/
10
1
6
/
10
4 10 45 125 450
4
/
10
1
8
/
10
4
1
/
2
12 50 150 500
1
/
2
2 5 15 60 175 600
6
/
10
2
1
/
4
5
6
/
10
17
1
/
2
70 200
8
/
10
2
1
/
2
6 20 75* 225
Note: All LLSRK_ID fuses rated 1 amp and above are Indicator
®
fuses.
*75 A is only available for the 600 V.
Web Resources
Download TC Curves, CAD drawings and other technical
information: littelfuse.com/llsrk
littelfuse.com/llnrk
Recommended Fuse Holders
LFR60 Series • LFR25 Series
1,000
10,000
100,000
PEAK LET- THRU IN AMPERES
600A -
400A -
200A -
100A -
60A -
30A -
12A -
5A -
3.5A -
10
100
10 100 1,000 10,000 100,000
AVAILABLE FAULT CURRENT
SYMMETRICAL R.M.S. AMPERES
BASIS FOR DATA:
TEST VOLTAGE: 600V
TIME CONSTANT/POW ER FACTOR: FUSE CATALOG NUMBER:
DRAWN BY:
DATE:
REVISION:
DRAWING NO.: SHEET
PEAK LETTHRUCHARACTERISTICCURVES
LITTELFUSE,INC.
CHICAGO,IL.USA
LLL
03/14/2016
A
2 OF 6
FCC05-LSRK
LLSRK & LLSRKID 3.5A - 600A
- DATA GENERATED IN EXCEL -
Peak Let-Thru Curve (600 V)
Note: For more information, see Peak Let-Thru Table
Dimensions
Please refer to the Class R dimensions page 3.
Ordering Information
TYPE SERIES AMP
CATALOG
NUMBER
ORDERING
NUMBER
INDICATING LLSRK_ID 60 LLSRK060ID LSRK060.TXID
NON-INDICATING LLSRK 60 LLSRK060 LSRK060.T
600 V
250 V
TYPE SERIES AMP
CATALOG
NUMBER
ORDERING
NUMBER
NON-INDICATING LLNRK 80 LLNRK080 LNRK080.V
LLSRK & LLSRKID
QP
L
POWR-GARD
®
Fuse Datasheet
© 2016 Littelfuse POWR-GARD
®
Products
Rev: 1-A-031716
littelfuse.com
2 of 3
CLASS RK1 – LLNRK • LLSRK • LLSRK_ID SERIES FUSES
SHORT CIRCUIT
CURRENT*
APPARENT RMS SYMMETRICAL CURRENT FOR VARIOUS FUSE RATINGS
3.5 A 5 A 12 A 30 A 100 A 200 A 400 A 600 A
5,000 196 251 427 586 1,764 2,821 - -
10,000 247 316 538 739 2,222 3,554 6,850 8,489
15,000 283 362 616 845 2,544 4,069 7,8 42 9,718
20,000 312 399 677 930 2,800 4,478 8,631 10,696
25,000 336 430 730 1,002 3,016 4,824 9,297 11,522
30,000 357 456 776 1,065 3,205 5,126 9,880 12,244
35,000 376 481 816 1,121 3,374 5,397 10,401 12,889
40,000 393 502 854 1,172 3,528 5,642 10,874 13,476
50,000 423 541 919 1,263 3,800 6,078 11,714 14,516
60,000 450 575 977 1,342 4,038 6,459 12,448 15,426
80,000 495 633 1,075 1,477 4,445 7,109 13,700 16,979
100,000 533 682 1,158 1,591 4,788 7,6 58 14,758 18,290
150,000 610 781 1,326 1,821 5,481 8,766 16,894 20,936
200,000 671 859 1,460 2,005 6,032 9,648 18,594 23,043
Current-Limiting Effects of LLSRK and LLSRK_ID (600 V) Fuses
SHORT CIRCUIT
CURRENT*
APPARENT RMS SYMMETRICAL CURRENT FOR VARIOUS FUSE RATINGS
30 A 60 A 100 A 200 A 400 A 600 A
5,000 900 1,400 2,000 2,700 4,800 5,000
10,000 1,100 1,900 2,700 3,500 6,200 8,500
15,000 1,250 2,100 3,100 4,200 7,000 9,500
20,000 1,400 2,400 3,500 4,600 8,000 10,800
25,000 1,500 2,600 3,900 5,000 8,300 11,500
30,000 1,600 2,800 4,000 5,250 9,000 12,000
35,000 1,700 2,850 4,300 5,500 9,500 12,500
40,000 1,800 3,000 4,600 5,800 9,800 13,500
50,000 1,900 3,200 4,800 6,300 10,200 14,000
60,000 2,000 3,500 5,200 6,700 11,000 15,000
80,000 2,200 3,900 5,700 7,2 00 12,200 16,000
100,000 2,300 4,000 6,000 8,100 12,700 17,000
150,000 2,500 4,500 6,700 9,100 14,000 19,000
200,000
2,600 4,800 7,000 9,700 15,000 20,000
*Prospective RMS Symmetrical Amperes Short-Circuit Current
Note: Data derived from Peak Let-Thru Curves
Current-Limiting Effects of LLNRK (250 V) Fuses
Blown Fuse Indicator Assembly
Granular Quartz Filling
Precision Formed Short Circuit Element
Fiberglass Reinforced Pultruded Body
Elastomeric Silicone Overload Section
Plated End Caps
LLSRK_ID Fuses—Quality Construction
for performance you can rely on…
Littelfuse LLSRK_ID Fuses feature true dual-element
construction. This robust design withstands
repeated surges within rated time delay
without opening needlessly, eliminating
downtime caused by power surges
or equipment demands.
POWR-GARD
®
Fuse Datasheet
© 2016 Littelfuse POWR-GARD
®
Products
Rev: 1-A-031716
littelfuse.com
3 of 3
CLASS RK1 – LLNRK • LLSRK • LLSRK_ID SERIES FUSES
AMPS
FIGURE
NUMBER
SERIES
DIMENSIONS INCHES (mm)
A B C D E F G H J K
1
/
10
–30
1
LLNRK 2 (50.8)
1
2
(12.7)
1
2
(12.7)
9
16
(14.3)
5
64
(2.0)
5
32
(4.0)
3
8
(9.5)
LLSRK
LSRK_ID
5 (12 7.0)
3
4
(19.1)
5
8
(15.9)
13
16
(20.6)
3
32
(2.4)
3
16
(4.8)
5
8
(15.9)
35 – 60
1
LLNRK 3 (76.2)
3
4
(19.1)
5
8
(15.9)
13
16
(20.6)
3
32
(2.4)
3
16
(4.8)
5
8
(15.9)
LLSRK
LSRK_ID
5
1
2
(139.7)
1 (25.4)
5
8
(15.9) 1
1
16
(27.0)
3
32
(2.4)
1
4
(6.4)
7
8
(22.2)
70 – 100
2
LLNRK
5
7
8
(149.2)
1 (25.4)
1
1
16
(27.0) 1
1
16
(27.0)
1
8
(3.2)
3
4
(19.1)
1
4
(6.4)
9
32
(7.1)
1
2
(12.7)
LLSRK
LSRK_ID
7
7
8
(200.0) 1
1
4
(31.8) 1
1
16
(27.0) 1
5
16
(33.3)
1
8
(3.2)
3
4
(19.1)
1
4
(6.4)
9
32
(7.1)
1
2
(12.7)
110 – 200
2
LLNRK
7
1
8
(181.0) 1
1
2
(38.1) 1
15
32
(3 7.3) 1
19
32
(40.5)
3
16
(4.8) 1
1
8
(28.6)
7
16
(11.1)
9
32
(7.1)
11
16
(17.5)
LLSRK
LLSRK_ID
9
5
8
(244.5) 1
3
4
(44.5) 1
15
32
(3 7.3) 1
27
32
(46.8)
3
16
(4.8) 1
1
8
(28.6)
7
16
(11.1)
9
32
(7.1)
11
16
(17.5)
225 – 400
2
LLNRK
8
5
8
(219.1)
2 (50.8)
1
15
16
(49.2) 2
3
32
(53.2)
1
4
(6.4) 1
5
8
(41.3)
5
8
(15.9)
13
32
(10.3)
15
16
(23.8)
LLSRK
LLSRK_ID
11
5
8
(295.3) 2
1
2
(63.5)
2 (50.8)
2
19
32
(65.9)
1
4
(6.4) 1
5
8
(41.3)
5
8
(15.9)
13
32
(10.3)
15
16
(23.8)
45 060 0 2
LLNRK
10
3
8
(263.5) 2
1
2
(63.5) 2
3
8
(60.3) 2
19
32
(65.9)
1
4
(6.4)
2 (50.8)
3
4
(19.1)
17
32
(13.5) 1
1
8
(28.6)
LLSRK
LLSRK_ID
13
3
8
(339.7)
3 (76.2)
2
13
32
(61.1) 3
3
32
(78.6)
1
4
(6.4)
2 (50.8)
3
4
(19.1)
17
32
(13.5) 1
1
8
(28.6)
A
F
E
C
D
G
B
A
J
K
H
B
C
F
D
70-600A
FIG. 1 FIG. 2
E
Dimensions

LSRK045.T

Mfr. #:
Manufacturer:
Description:
Industrial & Electrical Fuses 45A 600VAC 300VDC Class RK1
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union