TMC
100695_en_03 PHOENIX CONTACT 3
Switching capacity I
cn
TMC...0,2 A ... TMC...5 A
TMC...6 A ... TMC...16 A
Characteristic curve F1 and M1
400 A
800 A
2500 A (at 32 V DC)
Switching capacity I
N
(UL 1077)
1 and 2-pos.
3-pos.
1 and 2-pos.
I
N
= 0.2 A ... 16 A
277 V AC/5000 A
480 V AC/5000 A
65 V DC/2000 A
Degree of protection (IEC 60529)
Actuation area
Connection area
IP30
IP20
Vibration resistance
Characteristic curve F1
Characteristic curve M1
3g (57 Hz ... 500 Hz), ±0.23 mm (10 Hz ... 57 Hz)
53g (57 Hz ... 500 Hz), ±0.38 mm (10 Hz ... 57 Hz)
Test according to IEC 60068-2-6, Test Fc, 10 frequency cycles/axis
Shock resistance
Characteristic curve F1
Characteristic curve M1
25g (11 ms), shock direction 1, 2, 3, 4, 5; 10g (11 ms), shock direction 6
25g (11 ms), shock direction 1, 2, 3, 4, 5; 20g (11 ms), shock direction 6
Test according to IEC 60068-2-27, Test Ea
Corrosion resistance 96 hours in 5% salt fog
Test according to IE 60068-2-11, Text Ka
Humidity test 240 hours in 95% relative humidity
Test according to IE 60068-2-78, Text Cab
Weight 60 g per position, approximately
Technical data
Technical data according to IEC/DIN VDE
Impulse voltage withstand level 4 kV
Pollution degree 3
Auxiliary contact: maximum load current 1 A for 2.5 mm
2
Maximum cross-section with insertion bridge (solid and stranded) 1.5 mm
2
Surge voltage category III
Insulation material group I
Connection capacity Main contact Auxiliary contact
Connection capacity
Solid
Stranded
0.2 mm
2
... 6 mm
2
0.2 mm
2
... 4 mm
2
0.2 mm
2
... 2.5 mm
2
0.2 mm
2
... 1.5 mm
2
Connection capacity (stranded with ferrule)
Without plastic sleeve
With plastic sleeve
0.25 mm
2
... 4 mm
2
0.25 mm
2
... 2.5 mm
2
0.25 mm
2
... 2.5 mm
2
0.25 mm
2
... 1.5 mm
2
Two conductors with the same cross-section
Solid and stranded
Stranded with ferrule without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
0.2 mm
2
... 1 mm
2
0.2 mm
2
... 1 mm
2
0.5 mm
2
... 2.5 mm
2
0.2 mm
2
... 0.75 mm
2
0.2 mm
2
... 0.5 mm
2
0.5 mm
2
... 0.75 mm
2