0914439

100695_en_03
TMC
Data sheet
© PHOENIX CONTACT 2012-03-09
1Description
Single or multi-position thermomagnetic circuit breaker with
lever actuation, DIN rail mounting, trip-free mechanism that
cannot be influenced, various characteristic curves, all-pole
tripping.
The circuit breakers meet the requirements of circuit breaker
standard EN 60934 (IEC 60934): S-type, TM.
Typical areas of application are telecommunications
systems, power supply units, industrial switchgear and
control systems, and rail vehicles.
The ideal characteristic curve shown here illustrates the
curve of the thermomagnetic trigger characteristic. The time-
delayed tripping protects the thermal part of the
characteristic curve against overload. The magnetic part of
the circuit breaker responds without delay to high overload
and short-circuit currents and trips within a few milliseconds.
Figure 1 Ideal characteristic curve
Thermal tripping range
Magnetic tripping range
1
0,01
0,1
1
10
100
2 4 6 810 20
Multiples of the nominal current
t [s]
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog
.
This data sheet is valid for all products listed on the following page:
Thermomagnetic circuit breaker
for mounting on a DIN rail
TMC
100695_en_03 PHOENIX CONTACT 2
2Ordering data
2.1 Order key
Ordering example
TMC with 1-pos. main current path, one N/O contact,
medium-blow characteristic curve, and a nominal current of
2 A: TMC 1 M1 100 2A
3 Technical data
Thermomagnetic circuit breaker
Description Type Order No. Pcs./Pkt.
Thermomagnetic circuit breaker,
with universal foot for mounting on
3 or 4
TMC... (see order key) 6
Accessories
Description Type Order No. Pcs./Pkt.
Insertion bridge, insulated, 80-pos.
(I
max
: 50 A)
(For central supply I
N
: 80 A)
EB 80-12 3009338 1
Zack marker strip, 10-section, for labeling the center of the terminal block ZB 6 See CLIPLINE catalog
UniCard sheets, for labeling terminal blocks using a Zack marker strip
groove, 96-section, can be labeled with BLUEMARK and CMS-P1-PLOTTER,
color: white
UC-TM 5 0818108 10
Screwdriver SZS 0,6X3,5 1205053 10
Type Main
current paths
Characteristic
curves
Auxiliary
contact versions
Nominal
current
TMC 1 Single-pos.
2 Two-pos.
3 Three-pos.
F1 Thermal 1.05 x I
N
... 1.4 x I
N
,
magnetic 2 x I
N
... 4 x I
N
DC (fast-blow),
only for DC applications
M1 Thermal 1.05 - 1.4 I
N
,
magnetic 6 x I
N
... 12 x I
N
AC,
7.8 x I
N
... 15.6 x I
N
DC
(medium-blow)
100 Single-pos.: 1 N/O contact
200
Single-pos.: 1 N/C contact
120 Two-pos.: 1 N/O contact, 1 N/C
contact
122 Three-pos.: 1 N/O contact, 2 N/C
contacts
0.2 A 2.5 A
0.3 A 3 A
0.4 A 4 A
0.5 A 5 A
0.6 A 6 A
0.8 A 8 A
1 A 10 A
1.2 A 12 A
2A 15A
16A
Technical data
Nominal voltage 250 V AC (65 V DC),
3 433 V AC (50/60 Hz)
Nominal current range 0.2 A ... 16 A, see order key
Auxiliary circuit 240 V AC (65 V DC), 1 A
Service life 10,000 cycles with 1 x I
N
, inductive
Ambient temperature -30°C ... +60°C (T 60)
Insulation coordination (IEC 60664) 2.5 kV/2, increased insulation in the actuation area
Dielectric strength
Actuation area
Main to auxiliary circuit
Position to position
3000 V AC test voltage
3000 V AC test voltage
1500 V AC test voltage
Insulation resistance > 100 M (500 V DC)
TMC
100695_en_03 PHOENIX CONTACT 3
Switching capacity I
cn
TMC...0,2 A ... TMC...5 A
TMC...6 A ... TMC...16 A
Characteristic curve F1 and M1
400 A
800 A
2500 A (at 32 V DC)
Switching capacity I
N
(UL 1077)
1 and 2-pos.
3-pos.
1 and 2-pos.
I
N
= 0.2 A ... 16 A
277 V AC/5000 A
480 V AC/5000 A
65 V DC/2000 A
Degree of protection (IEC 60529)
Actuation area
Connection area
IP30
IP20
Vibration resistance
Characteristic curve F1
Characteristic curve M1
3g (57 Hz ... 500 Hz), ±0.23 mm (10 Hz ... 57 Hz)
53g (57 Hz ... 500 Hz), ±0.38 mm (10 Hz ... 57 Hz)
Test according to IEC 60068-2-6, Test Fc, 10 frequency cycles/axis
Shock resistance
Characteristic curve F1
Characteristic curve M1
25g (11 ms), shock direction 1, 2, 3, 4, 5; 10g (11 ms), shock direction 6
25g (11 ms), shock direction 1, 2, 3, 4, 5; 20g (11 ms), shock direction 6
Test according to IEC 60068-2-27, Test Ea
Corrosion resistance 96 hours in 5% salt fog
Test according to IE 60068-2-11, Text Ka
Humidity test 240 hours in 95% relative humidity
Test according to IE 60068-2-78, Text Cab
Weight 60 g per position, approximately
Technical data
Technical data according to IEC/DIN VDE
Impulse voltage withstand level 4 kV
Pollution degree 3
Auxiliary contact: maximum load current 1 A for 2.5 mm
2
Maximum cross-section with insertion bridge (solid and stranded) 1.5 mm
2
Surge voltage category III
Insulation material group I
Connection capacity Main contact Auxiliary contact
Connection capacity
Solid
Stranded
0.2 mm
2
... 6 mm
2
0.2 mm
2
... 4 mm
2
0.2 mm
2
... 2.5 mm
2
0.2 mm
2
... 1.5 mm
2
Connection capacity (stranded with ferrule)
Without plastic sleeve
With plastic sleeve
0.25 mm
2
... 4 mm
2
0.25 mm
2
... 2.5 mm
2
0.25 mm
2
... 2.5 mm
2
0.25 mm
2
... 1.5 mm
2
Two conductors with the same cross-section
Solid and stranded
Stranded with ferrule without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
0.2 mm
2
... 1 mm
2
0.2 mm
2
... 1 mm
2
0.5 mm
2
... 2.5 mm
2
0.2 mm
2
... 0.75 mm
2
0.2 mm
2
... 0.5 mm
2
0.5 mm
2
... 0.75 mm
2

0914439

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Circuit Breakers TMC 1 M1 100 1.0A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: