2803153

https://www.phoenixcontact.com/pi/products/2803153
08/19/2018Page1/4
Surge protection device-CN-UB-70DC-6-SB-2803153
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Attachment plug with surge protection for coaxial signal interfaces. Connection: N connector, male/female
Why buy this product
Mounting plate enables mounting, e.g., in a control cabinet
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356293204
Technical data
Dimensions
Height 24 mm
Width 24 mm
Depth 50 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 90 °C
Degree of protection IP68
IP68
General
Housing material Brass (CuZn)
Color nickel
Standards for cearances and creepage distances DIN VDE 0110-1
IEC60664-1
Mounting type Connection-specific intermediate plugging
Type Attachment plug
https://www.phoenixcontact.com/pi/products/2803153
08/19/2018Page2/4
Surge protection device-CN-UB-70DC-6-SB-2803153
Technical data
General
Direction of action Line-Shield/Earth Ground
Additional descriptions
Note
To meet the discharge conditions for DC voltages, please note the
following information: "The surge protective device should be used
together with a transmitter unit, which shuts down in the event of a short-
circuit."
Protective circuit
IEC test classification C2
C3
D1
VDE requirement class C2
C3
D1
Maximum continuous voltage U
C
70 V DC
50 V AC
Maximum continuous voltage U
C
(line-earth)
70 V DC
50 V AC
Rated current 10 A
Operating effective current I
C
at U
C
≤ 1 µA
Nominal discharge current I
n
(8/20) µs
5 kA
Nominal discharge current I
n
(8/20) µs (line-earth)
5 kA
Nominal discharge current I
n
(8/20) µs (line-shield)
5 kA
Total discharge current I
total
(8/20)µs
5 kA
Max. discharge current I
max
(8/20) µs maximum (line-earth)
10 kA
Max. discharge current I
max
(8/20)µs maximum (line-shield)
10 kA
Nominal pulse current Ian (10/1000) µs (Core-Shield) 100 A
Impulse discharge current (10/350)µs, peak value l
imp
1 kA
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 650 V
Output voltage limitation at 1 kV/µs (line-shield) spike ≤ 650 V
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 650 V
Output voltage limitation at 1 kV/µs (line-shield) static ≤ 650 V
Voltage protection level U
p
(line-earth)
≤ 800 V (C2 - 4 kV / 2 kA)
≤ 1 kV (C2 - 10 kV / 5 kA)
Voltage protection level U
p
(line-shield)
≤ 800 V (C2 - 4 kV / 2 kA)
≤ 1 kV (C2 - 10 kV / 5 kA)
Response time t
A
(line-earth)
≤ 100 ns
Response time tA (line-shield) ≤ 100 ns
Input attenuation aE, asym. 0.1 dB (≤ 6 GHz)
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system > 6 GHz
Frequency range 0 Hz ... 6 GHz
https://www.phoenixcontact.com/pi/products/2803153
08/19/2018Page3/4
Surge protection device-CN-UB-70DC-6-SB-2803153
Technical data
Protective circuit
Standing wave ratio SWR in a 50 Ω system typ. 1.15 (≤ 6 GHz)
Permissible HF power P
max
at VSWR = xx (50 ohm system)
30 W (VSWR = 1.15)
Capacity (line-earth) typ. 1.5 pF
Capacity asymmetrical (shield) typ. 1.5 pF
Surge protection fault message none
Impulse durability (line-earth) C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1 kA
Impulse durability (line-shield) C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1 kA
Alternating current carrying capacity (line-shield) 5 A - 1 s
Connection data
Connection method N connector 50 Ω
Connection method IN N connector, male
Connection method OUT N connector, female
Standards and Regulations
Standards/regulations IEC61643-21
Standards/specifications IEC61643-21 2000
Drawings
Circuit diagram
6
Dimensional drawing
50
23
24
16
Approvals
Approvals
Approvals
EAC / EAC
Ex Approvals

2803153

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Surge Suppressors CN-UB-70DC-6-SB
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet