14 Password (IDN S-0-00267)
In the default setting some parameters of the device are
write-protected with a password. If you try to change pass-
word-protected parameters without lifting the write protec-
tion, error 7009
hex
is output via the service channel (opera-
tion data is password write-protected).
The password can be changed and the write protection can
be activated or deactivated via IDN S-0-0267. Passwords
can only comprise UTF8 characters without spaces and are
stored retentively.
The default password is PW170875.
The list of password-protected parameters can be found in
IDN S-0-0279.
The following IDNs are password protected:
14.1 Change password
To change the password, the currently active password, the
new password, and, for confirmation, the new password
again must be sent to the device, each separated by a
space. Changing the password automatically activates write
protection for all password-protected parameters.
14.2 Activate write protection
There are three methods for activating password-protected
write protection:
Switch the power supply off and back on. Once the de-
vice is restarted, write protection is activated.
Overwrite the password parameter with something oth-
er than the password.
Change the existing password.
14.3 Deactivate write protection
The write protection is deactivated by overwriting the pass-
word parameter with the current password.
15 IP address assignment
The IP address is changed via the following IDNs:
The IP address can be changed via the Sercos parameter
S-0-1020.
The subnet mask can be changed via parameter S-0-1021
and the gateway address via parameter S-0-1022.
The IDN S-0-1048 is used to activate the IP address via
Sercos.
16 Monitoring connection (connection
setup, IDN S-0-1050.x.1)
The following connection monitoring mechanisms are sup-
ported (bit 0 and bit 1 of IDN S-0-1050.x.1):
Producer cycle, synchronous operation (00
bin
)
Asynchronous operation without watchdog (10
bin
)
17 Electronic rating plate (IDNs S-0-
1300.x.y)
The electronic rating plate comprises the IDNs S-0-
1300.x.y. See the table in the “Sercos parameter” section.
IDN Description
S-0-1020 IP address
S-0-1021 Subnet mask
S-0-1022 Gateway address
If the password is read via the service chan-
nel, the device will send the password as a
string with 3 “*” characters (UTF8 code 0x2A)
if the write protection is activated or as a string
with 3 “$” characters (UTF8-Code 0x24) if the
write protection is deactivated and not as
plain text.
IDN Description
S-0-1020 IP address
S-0-1021 Subnet mask
S-0-1022 Gateway address
S-0-1048 Procedure Command -
activation of the IP parameters
All parameters are password-protected. For
further information, please refer to the “Pass-
word” section.
The modified IP address parameters are not
stored retentively on the device. In the case of
a voltage reset, these parameters need to be
re-transmitted.
AXL E S3 DI16 M12 6P
8561_en_04 PHOENIX CONTACT 20
18 Diagnostics: I/O and channel errors
Sercos enables the Sercos device to store diagnostic infor-
mation together with the error location and error type.
Diagnostic messages are enabled by default, but can be dis-
abled via a parameter on startup.
The Sercos master is informed that diagnostic information
that has been entered.
If at least one item of diagnostic information has been
stored, this is indicated by the S and SD LEDs.
The following Sercos diagnostic messages are indicated by
the Sercos slave:
Overtemperature of the device
–Surge voltage of U
S
Overload of U
S
Undervoltage of U
S
I/O and channel errors are mapped in the following diagnos-
tic IDNs according to Sercos specifications.
19 Mapping the I/Os to Sercos
The device has just one Sercos module and therefore only
has one structure instance 0.
The I/Os are assigned to the structure instances and IO
function groups according to the Sercos IO profile.
The following function groups are defined:
The cyclical data of the Sercos device is mapped to the IDNs
S-0-1502 and S-0-1503 according to FSP_IO.
The device supports the following IDNs as configurable
data:
IDN Description
S-0-0095 Diagnostic message
S-0-0390 Diagnostic number
S-1500.0.32 IO diagnostic message
S-1500.0.33 Current IO diagnostic message
S-1303.0.10 Diagnostic trace buffer no 1
S-1303.0.11 Diagnostic trace buffer no 2
S-1303.0.12 Diagnostic trace buffer no 3
Function group
(FG_IO)
Name
S-0-1502 IO function group digital output
S-0-1503 IO function group digital input
In a producer connection In a consumer connection
S-0-1500.0.2 S-0-1500.0.1
S-0-1500.0.9 S-0-1500.0.1
FG_IO.x.9 FG_IO.x.5
FG_IO.x.13 FG_IO.x.11
S-0-0390 S-0-0390
This information is stored in:
S-0-0187 S-0-0188
AXL E S3 DI16 M12 6P
8561_en_04 PHOENIX CONTACT 21
19.1 Assignment of the terminal points to the IN process data (S-0-1503.0.09)
The data is mapped as follows:
Key:
19.2 Assignment of the DIAGIN process data (S-0-1502.0.17/S-0-1503.0.17)
4 bytes of DIAG IN data are available per function group.
Input process data (S-0-1503.0.09)
Byte Byte 0 Byte 1
Bit 7654321076543210
IN 07 06 05 04 03 02 01 00 17 16 15 14 13 12 11 10
Connection X04 X03 X02 X01 X08 X07 X06 X05
Pin 2424242424242424
DI 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9
Bit: Process data assignment
IN: LED marking
DI: Input of the device
Bit 31 ... bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Supply of the module electronics and sensors (U
S
) Reserved
Reserved Undervoltage Overload Reserved
Not all diagnostic data is mapped to the process data, see also “Diagnostics: I/O and channel errors”.

2701544

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL E S3 DI16 M12 6P
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet