B88069X4230C101

Surge arrester
2-electrode arrester
Series/Type: V12-H30X
Ordering code: B88069X4230C101
Date: 2016-05-25
Version: 03
EPCOS AG 2016. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and then
change the color to "white". This ensures that the table disappears (invisible) for the customer PDF.
Don't change formatting when entering or pasting text in the table and don't add any cell or line in and to it!
Identification/Classification 1
(header 1 + top left bar):
Surge arrester
Identification/Classification 2
(header 2 + bottom left header bar):
2-electrode arrester
Ordering code: (top right header bar)
B88069X4230C101
Series/Type: (bottom right header bar)
V12-H30X
Preliminary data (optional):
Department:
PPD AB PD / PPD AB PM
Date:
2016-05-25
Version: 03
Surge arrester B88069X4230C101
2-electrode arrester V12-H30X
PPD AB PD / PPD AB PM 2016-05-25
Please read Cautions and warnings and Page 2 of 4
Important notes at the end of this document.
Features Applications
Standard size
Maximum current rating
Fast response time
Stable performance over life
Low capacitance
High insulation resistance
RoHS-compatible
Industry
Electrical specifications
DC spark-over voltage
1) 2)
Tolerance
Min.
Max.
3000
±25
2250
3750
V
%
V
V
Impulse spark-over voltage
at 100 V/µs - for 99% of measured values
- typical values of distribution
at 1 kV/µs - for 99% of measured values
- typical values of distribution
< 4500
< 4300
< 5000
< 4500
V
V
V
V
Service life
10 operations 50 Hz, 1 s 20 A
1 operations 50 Hz, 0.18 s (9 cycles) 120 A
10 operations 8/20 µs 20 kA
1 operation 8/20 µs 30 kA
Insulation resistance at 100 V
DC
> 1
G
Capacitance at 1 MHz < 1.5
pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 35
< 1
~ 200
V
A
V
Weight ~ 11 g
Operation and storage temperature
40 ... +125
°C
Climatic category (IEC 60068-1) 40/125/21
Marking, black positive
3000 YY O
3000 - Nominal voltage
YY - Year of production
O - Non radioactive
1)
At delivery AQL 0.65 level II, DIN ISO 2859
2)
In ionized mode
Terms in accordance with ITU-T Rec. K.12; IEC 61663-2 and IEC 61643-311.
Surge arrester B88069X4230C101
2-electrode arrester V12-H30X
PPD AB PD / PPD AB PM 2016-05-25
Please read Cautions and warnings and Page 3 of 4
Important notes at the end of this document.
Dimensional drawing in mm
Ordering code and packing advice
B88069X4230C101 = 10 pcs. in container
Cautions and warnings
Do not operate surge arresters in power supply networks, whose maximum operating voltage
exceeds the minimum spark-over voltage of the surge arresters.
Surge arresters may become hot in the event of longer periods of current stress (burn risk). In the
event of overload the connectors may fail or the component may be destroyed.
Surge arresters must be handled with care and must not be dropped.
Do not continue to use damaged surge arresters.
Display of ordering codes for EPCOS products
The ordering code for one and the same EPCOS product can be represented differently in data
sheets, data books, other publications, on the EPCOS website, or in order-related documents such as
shipping notes, order confirmations and product labels. The varying representations of the
ordering codes are due to different processes employed and do not affect the specifications of
the respective products. Detailed information can be found on the Internet under
www.epcos.com/orderingcodes

B88069X4230C101

Mfr. #:
Manufacturer:
EPCOS / TDK
Description:
Gas Discharge Tubes / Gas Plasma Arrestors V12-H30X
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet