2800107

https://www.phoenixcontact.com/pi/products/2800107
08/18/2018Page1/4
Combination type 1/2 protective device-FLT 60-400-2800107
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Type 1 / Class I / B arrester (lightning current arrester) with arc chopping spark gap, 1-channel. Housing
width: 35 mm (2 div.)
Why buy this product
High discharge capacity
1-channel
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356479936
Technical data
Dimensions
Height 90 mm
Width 35.5 mm
Depth 65.5 mm
Horizontal pitch 2 Div.
Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
General
IEC test classification I
T1
https://www.phoenixcontact.com/pi/products/2800107
08/18/2018Page2/4
Combination type 1/2 protective device-FLT 60-400-2800107
Technical data
General
EN type T1
IEC power supply system TN-S
TN-C
TT
Mode of protection L-PEN
Mounting type DIN rail: 35 mm
Color black
Housing material PA 6.6
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, one-piece
Number of positions 1
Surge protection fault message none
Protective circuit
Nominal voltage U
N
230/400V AC (TN)
230/400V AC (TT)
Nominal frequency f
N
50 Hz (60Hz)
Maximum continuous operating voltage U
C
(L-PEN)
400 V AC
Rated load current I
L
80 A
Residual current I
PE
< 0.1 mA
Standby power consumption P
C
≤ 40 mVA
Nominal discharge current I
n
(8/20) µs (L-PEN)
60 kA
Impulse discharge current (10/350) µs (L-PEN), charge 30 As
Impulse discharge current (10/350) µs (L-PEN), specific energy 900 kJ/Ω
Impulse discharge current (10/350)µs (L-PEN), peak current value I
imp
60 kA
Follow current interrupt rating I
fi
(L-PEN)
2.5 kA
Short-circuit current rating I
SCCR
2.5 kA
Voltage protection level U
p
(L-PEN)
≤ 5 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 5 kV
TOV behavior at U
T
(L-PEN)
440 V AC (5s / withstand mode)
440 V AC (120min / withstand mode)
Response time t
A
(L-PEN)
≤ 100 ns
Max. backup fuse with V-type through wiring 80 A AC (gG)
Max. backup fuse with branch wiring 500 A AC (gG)
Connection data
Connection method Screw connection
Screw thread M6
Tightening torque 8 Nm
Stripping length 17 mm
https://www.phoenixcontact.com/pi/products/2800107
08/18/2018Page3/4
Combination type 1/2 protective device-FLT 60-400-2800107
Technical data
Connection data
Conductor cross section flexible min. 16 mm²
Conductor cross section flexible max. 35 mm²
Conductor cross section solid min. 10 mm²
Conductor cross section solid max. 50 mm²
Conductor cross section AWG 6 ... 1
Standards and Regulations
Standards/regulations IEC61643-11 2011
EN61643-11 2012
Drawings
Dimensional drawing
90
45
65,5
58
51,5
Circuit diagram
L/N() L/N()
Approvals
Approvals
Approvals
EAC
Ex Approvals
Approval details
EAC
RU C-
DE.A*30.B01561

2800107

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Surge Suppressors FLT 60-400
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet