https://www.phoenixcontact.com/pi/products/2308098
08/19/2018Page2/4
Universal current transducer-MCR-SL-CUC-600-I-2308098
Technical data
Input data
Overload capacity
3 x I
IN
Frequency measuring range 20 Hz ... 6000 Hz (0 Hz)
Connection method Cable design: 32 mm diameter
Rated frequency: Standard converter 20 Hz ... 6000 Hz
Primary rated current I
pn
600 A
Output data
Output name Current output
Current output signal 4 mA ... 20 mA
Max. output current < 25 mA
Load/output load current output < 300 Ω
Connection method Screw connection
Switching output
Output name No switching output
Power supply
Nominal supply voltage 24 V DC
Supply voltage range 20 V DC ... 30 V DC
Max. current consumption
(30 + I
OUT
) mA
Connection data
Conductor cross section solid min. 0.25 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Stripping length 10 mm
General
Accuracy class 1
Maximum transmission error <± 1 % (of final value)
Temperature coefficient, typical 0.02 %/K (0 ... 60 °C)
0.04 %/K (-40°C...65°C)
Linearity error <± 1 % (From the range end value)
Step response (10-90%) 150 ms
Overvoltage category III
Degree of pollution 2
Rated insulation voltage 300 V AC
Test voltage input/output 3.5 kV (50 Hz, 1 min.)
Test voltage input/power supply 3.5 kV (50 Hz, 1 min.)
Noise emission EN 61000-6-4