Filter* Rated current Typical drive Leakage current*** Power loss Input Output Weight
@ 50°C (40°C) power rating** @ 520/760 VAC/50 Hz @ 25°C/50 Hz connections connections
[A] [kW] [mA] [W] [kg]
FN 258-7-.. 7 (7.7) 4 2.0 9 -29 -07 -29 1.0
FN 258-16-.. 16 (17.5) 7.5 2.1 20 -29 -07 -29 1.4
FN 258-30-.. 30 (33) 15 2.9 21 -33 -07 -33 1.7
FN 258-42-.. 42 (46) 22 3.0 30 -33 -07 -33 2.5
FN 258-55-.. 55 (60) 30 3.0 30 -34 -07 -34 2.9
FN 258-75-34 75 (82) 37 3.0 24 -34 -34 3.9
FN 258-100-35 100 (110) 55 3.0 51 -35 -35 5.5
FN 258-130-35 130 (143) 75 3.5 50 -35 -35 6.9
FN 258-180-.. 180 (197) 90 3.5 73 -40 -07 -40 11.0
FN 258-250-.. 250 (275) 132 3.4 79 -40 -07 -40 12.0
FN 258 HV-7-29 7 (7.7) 5.5 1.6 9 -29 -29 1.0
FN 258 HV-16-29 16 (17.5) 11 2.3 20 -29 -29 1.5
FN 258 HV-30-33 30 (33) 22 2.3 21 -33 -33 1.8
FN 258 HV-42-33 42 (46) 30 2.6 30 -33 -33 2.6
FN 258 HV-55-34 55 (60) 45 2.6 30 -34 -34 3.0
FN 258 HV-75-34 75 (82) 55 2.6 24 -34 -34 4.3
FN 258 HV-100-35 100 (110) 90 2.6 51 -35 -35 5.6
FN 258 HV-130-35 130 (143) 110 2.9 50 -35 -35 7.1
FN 258 HVIT-7-29 7 (7.7) 5.5 0.1 9 -29 -29 1.0
FN 258 HVIT-16-29 16 (17.5) 11 0.1 20 -29 -29 1.5
FN 258 HVIT-30-33 30 (33) 22 0.1 21 -33 -33 1.8
FN 258 HVIT-42-33 42 (46) 30 0.1 30 -33 -33 2.6
FN 258 HVIT-55-34 55 (60) 45 2.6 30 -34 -34 3.0
FN 258 HVIT-75-34 75 (82) 55 2.6 24 -34 -34 4.3
FN 258 HVIT-100-35 100 (110) 90 2.6 51 -35 -35 5.6
FN 258 HVIT-130-35 130 (143) 110 2.9 50 -35 -35 7.1
FN 258 L-7-.. 7 (7.7) 4 0.1 9 -29 -07 -29 1.0
FN 258 L-16-.. 16 (17.5) 7.5 0.1 20 -29 -07 -29 1.4
FN 258 L-30-.. 30 (33) 15 0.1 21 -33 -07 -33 1.7
FN 258 L-42-.. 42 (46) 22 0.1 30 -33 -07 -33 2.5
FN 258 L-55-.. 55 (60) 30 0.1 30 -34 -07 -34 2.9
FN 258 L-75-34 75 (82) 37 0.1 24 -34 -34 3.9
FN 258 L-100-35 100 (110) 55 0.1 51 -35 -35 5.5
FN 258 L-130-35 130 (143) 75 0.1 50 -35 -35 6.9
FN 258 L-180-.. 180 (197) 90 0.1 73 -40 -07 -40 11.0
FN 258 L-250-07 250 (275) 132 0.1 79 -40 -07 12.0
FN 258 P-7-.. 7 (7.7) 4 0.4 9 -29 -07 -29 1.0
FN 258 P-16-.. 16 (17.5) 7.5 0.4 20 -29 -07 -29 1.4
FN 258 P-30-.. 30 (33) 15 0.4 21 -33 -07 -33 1.7
FN 258 P-42-.. 42 (46) 22 0.4 30 -33 -07 -33 2.5
FN 258 P-55-.. 55 (60) 30 0.4 30 -34 -07 -34 2.9
FN 258 P-75-34 75 (82) 37 0.4 24 -34 -34 3.9
FN 258 P-100-35 100 (110) 55 0.4 51 -35 -35 5.5
FN 258 P-130-35 130 (143) 75 0.4 50 -35 -35 6.9
FN 258 P-180-.. 180 (197) 90 0.4 73 -40 -07 -40 11.0
FN 258 P-250-07 250 (275) 132 0.4 79 -40 -07 12.0
*
**To compile a complete part number, please replace the -.. with the required output connection style.
**
*Calculated at rated current, 440 VAC (FN 258)/690 VAC (FN 258 HV ) and cos phi=0.8. The exact value depends upon the efficiency of the drive, the motor and the entire
***application.
*** Standardized calculated leakage current acc. IEC60939 under normal operating conditions (FN 258 at 520 VAC and FN 258 HV at 760 VAC).