2904959

https://www.phoenixcontact.com/us/products/2904959
05/18/2015Page1/5
Repeater power supply-MACX PL-EX-RPSSI-2I-2904959
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i measuring transducer power supply and input signal conditioner, HART-transparent. Transfers supplied or
active 0/4 - 20 mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical
isolation, PLd, screw connection
Product Features
Key commercial data
Packing unit 1 pc
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 12.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
https://www.phoenixcontact.com/us/products/2904959
05/18/2015Page2/5
Repeater power supply-MACX PL-EX-RPSSI-2I-2904959
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Degree of protection IP20
Input data
Signal input Repeater power supply operation
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (20mA)
> 15.1 V (23mA)
Voltage drop approx. 3.9 V
Signal input Signal conditioner operation
Current input signal 4 mA ... 20 mA
Voltage drop approx. 3.9 V
Output data
Signal output Repeater power supply operation
Current output signal 4 mA ... 20 mA (active)
Load/output load current output < 450 Ω (20mA)
< 380 Ω (23mA)
Output ripple
< 20 mV
rms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal output Signal conditioner operation
Current output signal 4 mA ... 20 mA (active)
Load/output load current output < 450 Ω (20mA)
< 380 Ω (23mA)
Output ripple
< 20 mV
rms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Power supply
Designation Repeater power supply operation
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption < 75 mA (24VDC / 20mA)
Power consumption < 1.45 W (24 V DC/ 20 mA)
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
https://www.phoenixcontact.com/us/products/2904959
05/18/2015Page3/5
Repeater power supply-MACX PL-EX-RPSSI-2I-2904959
Technical data
Connection data
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 7 mm
Screw thread M3
Connection method Screw connection
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
General
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 1.3 ms (for 4 mA ... 20 mA step)
Status display Green LED (PWR supply voltage)
Inflammability class according to UL 94 V0
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Housing material PA 66-FR
Color yellow
Designation Input/output/power supply
Electrical isolation
300 V
rms
(Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output 1/output 2
Electrical isolation 1.5 kV AC (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326
ATEX  II (1) G [Ex ia Ga] IIC/IIB
 II (1) D [Ex ia Da] IIIC
 II 3 (1)G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx [Ex ia Ga] IIC/IIB
[Ex ia Da]
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA / Canada UL 61010
Class I Div 2; IS for Class I, II, III Div 1

2904959

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Safety Relays MACX PL-EX-RPSSI-2I
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet