1017513 TDPT 2,5/ 12-SP-5,08
REF 1017503 PHOENIX CONTACT 8 / 12
© PHOENIX CONTACT 2018
2018-04-23
Product version 00
Document revision 00
10 Electrical tests
Rated current / conductor cross section 32 A / 2.5 mm²
Rated insulation voltage (III/2) 400 V
Rated surge voltage (III/2) 4 kV
Contact resistance 1.13 mΩ
Degree of pollution 2
Specification IEC 60947-1:2007-06 + A1:2010-12
Mains type unearthed mains
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage 320 V 400 V 630 V
Rated surge voltage 4 kV 4 kV 4 kV
Degree of pollution 3 2 2
Overvoltage category III III II
Minimum clearance case A (inhomogeneous field) 3 mm 3 mm 3 mm
Minimum value of the creepage path requirement in acc. with table 4 mm 3 mm 3.2 mm
10.2 Air clearances and creepage distances
Specification IEC 60947-7-4:2013-08
Result Test passed
Conductor cross section/short-time current 4 mm² / 144 A
10.3 Short-time withstand current test
Specification IEC 60947-7-4:2013-08
Result Test passed
Contact resistance R
1
1.13 mΩ / 4 mm²
Test sequence 1: low temperature storage -40 °C / 2 h
Test sequence 2: heat storage 168 h/105 °C
Test sequence 3: noxious gas storage
(ISO 6988)
KFW 0.2 S/1 cycle
Contact resistance R
2
1.13 mΩ / 4 mm²
Rated impulse voltage at sea level
Voltage waveform ≥ (1.2/50 μs)
4.8 kV
Power-frequency withstand voltage
Voltage waveform ≥ (50/60 Hz)
3.1 kV
10.4 Aging test (climatic impact and corrosion testing)
Specification IEC 60512-3-1:2002-02
Result Test passed
10.5 Insulation resistance