HEC-RW-RLB-R

Catalog Data — Insulating Boots
Catalog
Numbers Type
2A0660 Single Conductor
2A0661 Two Conductor
Insulating boots are not included with non-breakaway parts
and must be ordered separately. They come standard with the
breakaway series. When boots are utilized, extra heat retention
requires that fuses are sized at a minimum of 200% of the RMS
load current.
TRON
®
In-Line Fuseholders HEC, HEG,
Single-Pole for SC Type Fuses HEH Series
Form No. HEC, HEG, and HEH Series
Page 1 of 2
Data Sheet: 2124
Bussmann
®
Non-Breakaway Holders
HEC Series Catalog Symbol: HEC-AA
In-Line Fuseholders, Single-Pole
Water-Resistant
For breakaway holders, see page 2.
Copper Crimp Terminals for (1) #12 to #8 solid or stranded
copper wires or
(2) #12 solid or stranded copper
wires
HEC — For SC-25, & SC-30 fuses.; 30A, 480V (or less).
Fuse size ⁄‹Ω£™∑ ≈ 1fiΩ•∑. Holder rated 30A, 600V.
Non-Breakaway Holders
HEG Series Catalog Symbol: HEG-AA
In-Line Fuseholders, Single-Pole
Water-Resistant
Copper Crimp Terminals for (1) #12 to #8 solid or stranded
copper wires or
(2) #12 solid or stranded copper
wires
HEG — For SC fuses; 0-15A, 600V (or less).
Fuse size ⁄‹Ω£™∑ ≈ 1fiΩ¡§∑. Holder rated 15A, 600V.
Recommended Torque on Coupling Nut: 10-20 in-lb.
Non-Breakaway Holders
HEH Series Catalog Symbol: HEH-AA, HEH-AB, and
HEH-AD
In-Line Fuseholders, Single-Pole
Water-Resistant
Agency Information:
CSA Certified, Class 6225-01, File 47235
HEH — For Type SC-20 fuses; 20A, 600V (or less). Also fuse
types BBS & KTQ (nominal size ⁄‹Ω£™∑ 1‹Ω•∑). Holder rated
20A, 600V. (CSA current rating - 15A)
Ordering Information:
Example:
A single-pole, in-line holder for a SC-20 fuse. A single #8
stranded copper wire is on the load. Copper crimp connec-
tion desired. Two #6 stranded copper wires are on the line
side. Copper crimp is the desired connection.
1. Choose HEH- Series.
2. Choose “A” for load side.
3. Choose “D” for line side.
Complete Part Number: HEH-AD
Fuse Holder Load Line
(HEC, HEG, Terminal Terminal
HEH)
7-16-03
N03082
TRON
®
In-Line Fuseholders HEC, HEG,
Single-Pole for SC Type Fuses HEH Series
Bussmann
®
Breakaway Holders
HEC Series Catalog Symbol: HEC-RW-RLB-R
In-Line Fuseholders, Double-Pole
Example:
A single-pole, in-line, breakaway holder for a SC-25 fuse. A sin-
gle #2 stranded, aluminum wire, crimp connection on the load
side. A single #2 stranded aluminum wire, crimp connection is
also on the line side.
1. Choose HEC- Series.
2. Choose “R” designation from page 1 for load side.
3. Choose “W” for breakaway option.
4. Choose “RLB-R” for breakaway receptacle on line side.
Full Catalog Number: HEC-RW-RLB-R.
Recommended Torque on Coupling Nut: 10-20 in-lb.
Catalog and Specification Data
Breakaway Receptacles
Conductor Data
Terminal Type Size Catalog
Symbol
Line
Terminals
Aluminum Crimp
#1 to #2 1 - -RLB-R
Solid Breakaway
(Required with W
breakaway
receptacle)
No. Per
Terminal
Solid
Stranded
Form No. HEC, HEG, and HEH Series
Page 2 of 2
Data Sheet: 2124
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con-
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Fuse Holder Load (Required) Line
(HEC) Terminal Terminal
W
Ordering Information:
7-16-03
N03082

HEC-RW-RLB-R

Mfr. #:
Manufacturer:
Bussmann / Eaton
Description:
Fuse Holder In-Line Tron
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet