Axioline F XC, Temperature recording module, Analog inputs: 8 (for resistance temperature
detectors), connection method: 2, 3, 4-wire (shielded), transmission speed in the local bus: 100 Mbps,
Extremeconditions version, including bus base module and AxiolineF connectors
The figure shows the standard item
Product Description
The module is designed for use within an AxiolineF station.
It is used to acquire signals from resistive temperature sensors.
The module supports all common platinum and nickel sensors according to DINEN60751 and SAMA.
Cu10, Cu50, Cu53 sensors as well as various KTY8x sensor types are also supported.
Why buy this product
8 analog input channels for the connection of resistance temperature detectors (RTD)
500 Ω and 5 kΩ linear inputs
Connection of sensors in 2, 3, and 4-wire technology
Integrated, digital sensor linearization
Standardized measured value representation directly in °C, °F or Ω
Measured value display in 16-bit format or floating point format
Programmable filters
Short-circuit protected inputs
Device rating plate stored
Diagnostic and status indicators
Can be used under extreme ambient conditions
Extended temperature range of -40°C ... +70°C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Partially coated PCBs
Temperature stability
Very high level of noise immunity
Low noise emission
Installation monitoring by means of “Channel scout” function
Key Commercial Data
Packing unit 1 STK
GTIN
https://www.phoenixcontact.com/pi/products/2701235
08/19/2018Page2/6
I/O module-AXL F RTD8 XC 1F-2701235
GTIN 4046356730471
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Caption Dimensional drawing
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions
The depth is valid when a TH35-7,5 DIN rail is used (according to
EN60715).
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under
extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000m above sea level)
Degree of protection IP20
General
Mounting type DIN rail
Net weight 215 g
Note on weight specifications with connectors and bus base module
Interfaces
Designation AxiolineFlocal bus
No. of channels 2
Connection method Bus base module
Transmission speed 100 Mbps
Axioline potentials
Designation
AxiolineF local bus supply (U
Bus
)
Supply voltage 5 V DC (via bus base module)
Current consumption typ. 115 mA
max. 180 mA
Power consumption typ. 0.58 W
max. 0.9 W
Designation
Supply for analog modules (U
A
)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
https://www.phoenixcontact.com/pi/products/2701235
08/19/2018Page3/6
I/O module-AXL F RTD8 XC 1F-2701235
Technical data
Axioline potentials
Current consumption typ. 15 mA
max. 25 mA
Power consumption max. 0.6 W
typ. 0.94 W (at U
Bus
and U
A
)
max. 1.5 W (at U
Bus
and U
A
)
Type of protection Surge protection of the supply voltage
Polarity reversal protection of the supply voltage
Transient protection
Analog inputs
Number of inputs 8 (for resistance temperature detectors)
Input name Analog inputs
Description of the input Inputs for resistive temperature sensors
Connection method Push-in connection
Connection technology 2, 3, 4-wire (shielded)
Sensor types (RTD) that can be used Pt, Ni, KTY, Cu sensors
Linear resistance measuring range 0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
Nominal value of the current sources
1 mA (Pt 100, Ni 100, R
Lin
500 Ω; pulse current, the specification is valid
during the sampling phase)
Measured value representation 16 bits (15 bits + sign bit)
Resolution A/D 24 bit
Type of protection Short-circuit protection, overload protection of the inputs
Transient protection of inputs
Transient protection of sensor supplies
Data formats IB IL, S7-compatible
Input filter time 40 ms
Electrical isolation
Test section
5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1
min.
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min.
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.
Standards and Regulations
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

2701235

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F RTD8 XC 1F