PDUMH30HVAT

5kW Single-Phase ATS/Metered PDU, 208/240V
Outlets (16 C13, 2 C19 & 1 L6-30R) 2 L6-30P 10ft
inputs, 2U Rack-Mount, TAA
MODEL NUMBER: PDUMH30HVAT
Description
Tripp Lite Metered ATS / Auto Transfer Switch provides a redundant power option for single-corded
network devices. Dual input cords support separate connection to PRIMARY and SECONDARY power
sources. The ATS will normally maintain continuous output to all outlets as derived from the primary input
cable. If the primary power source becomes unstable or fails altogether, the ATS will switch over to the
secondary power source until the primary input is restored and stable. Highly reliable solid-state switching
between primary and secondary inputs occurs in 1-5 milliseconds. ATS functionality is supported by any
two compatible AC power sources, regardless of phase angle, to support a variety of advanced redundant
power networking applications. Enables fault tolerant hot-swappable UPS protection when used with a
single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system.
In a two-UPS environment, the primary input cable must be supported by a full time sine wave UPS with
zero transfer time. Tripp Lite SmartOnline series is highly recommended for use as the primary UPS in a
two-UPS application. ATS configurations utilizing separate mains circuits, backup generators and even
separate utility power grid feeds are fully supported. On-board ATS processor constantly evaluates power
quality on both input sources to prevent transfer to the secondary source when unavailable or of lower
quality than the primary source. Front input LED's display primary or secondary power availability.
Features
208/240V 30A Automatic Transfer Switch (ATS) / Metered PDU (Agency de-rated to 24A continuous)
ATS features provide redundant power for critical network equipment with a single input power cord
Digital display with selection button reports voltage, amperage and kilowatt loading information in four
output segments (Segment 1: 8 C13 & 1 C19 outlets / Segment 2: 8 C13 & 1 C19 outlets / Segment 3:
L6-30R outlet / Segment 4: total output of all outlets combined)
19 built-in outlets (16 C13, 2 C19, 1 L6-30R)
Highlights
Single phase 30A 208/240V
Auto Transfer Switch / ATS
Metered PDU with Solid State
Switching
Enables redundant-power
configurations for single-corded
network devices
Separate primary & secondary
inputs connect to any two
compatible power sources
2U horizontal rackmount; 2 L6-
30P inputs; 19 outlets (16 C13,
2 C19, 1 L6-30R)
Front panel digital display with
LED indicators reports output
amps in 4 loading segments,
plus total kW and input voltage
Trade Agreements Act / TAA
Compliant for GSA Schedule
purchases
Package Includes
Auto Transfer Switch PDU
Rackmount installation brackets
Installable plug-retention
shelves & cable ties
1 / 4
Specifications
Set of two 10 ft. / 3m NEMA L6-30P input cables support connection to separate PRIMARY and
SECONDARY power sources
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails
or becomes unstable, the ATS will switch to maintain output as sourced from the secondary input cable
until power on the primary input is restored and stable
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS
and fully redundant UPS protection when each cord is connected to a separate UPS system (in a 2 UPS
environment, the primary input must be connected to an online double conversion UPS similar to Tripp
Lite SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate
out of phase utility power grid feeds are fully supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the
secondary source when unavailable or of lower quality than the primary source
Super-fast switchover between primary and secondary power sources occurs in 1-5 milliseconds
Front panel LEDs confirm power availability on both input lines
Trade Agreements Act / TAA Compliant for GSA Schedule purchases
OVERVIEW
UPC Code 037332159212
PDU Type Metered; Auto-Transfer Switch
OUTPUT
Output Capacity Details 5kW (208/240V), 4.8kW (200V) total capacity / 30A max (Agency de-rated to 24A), 24A max per L6-30R outlet; 20A
max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (16) C13; (2) C19; (1) L6-30R
Output Nominal Voltage 200; 208; 240
Overload Protection Includes two 20A output circuit breakers; Breaker 1 controls the upper row of 9 outlets (8 C13, 1 C19); Breaker 2
controls the lower row of outlets (8 C13, 1 C19); L6-30R outlet is unbreakered
INPUT
PDU Input Voltage 200; 208; 240
Recommended Electrical Service 30A 208V
Maximum Input Amps 30
Maximum Input Amps Details Agency de-rated to 24A continuous
PDU Plug Type (2) NEMA L6-30P
2 / 4
Input Cord Details Set of two inputs connect to separate PRIMARY and SECONDARY power sources
Input Cord Length (ft.) 10
Input Cord Length (m) 3.05
Input Phase Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Digital display reports output amps in 4 separately metered loading segments (BANK 1: Outlets #1-9; BANK 2:
Outlets #10-18; BANK 3: Outlet #19), whole-PDU output kW load level and input voltage on primary and secondary
input lines
Front Panel LEDs Front panel LEDs confirms amp / kilowatt / voltage reporting information
Switches ENTER and MODE switches toggle the digital display to show output amps (Banks 1-4), total kW output and input
voltage (primary, secondary)
PHYSICAL
Minimum Required Rack Depth
(inches)
16
Minimum Required Rack Depth (cm) 40.64
Shipping Dimensions (hwd / in.) 7.700 x 16.700 x 19.300
Shipping Dimensions (hwd / cm) 19.56 x 42.42 x 49.02
Shipping Weight (lbs.) 20.3000
Shipping Weight (kg) 9.21
Unit Dimensions (hwd / in.) 3.5 x 17.5 x 12.5
Unit Dimensions (hwd / cm) 8.8 x 44.4 x 31.7
Unit Weight (lbs.) 13.7
Unit Weight (kg) 6.21
Material of Construction Metal
Form Factors Supported 2U rackmount
PDU Form Factor Horizontal (2U)
ENVIRONMENTAL
Storage Temperature Range 5 to 122F (-15 to 50C)
Relative Humidity 5 to 95% (non-condensing)
Operating Elevation (ft.) 0-10,000
Operating Elevation (m) 0-3000
CERTIFICATIONS
Certifications Tested to UL 60950-1 (USA, Canada), Class A (Emissions), NOM (Mexico), RoHS Complaint, TAA Compliant
WARRANTY
3 / 4