4420.0408

4
Thermal-magnetic (TM and AS-line)
AS168XAC4
www.schurter.com /PG20
Circuit Breakers
Symbol Standard Rated current Rated voltage AC Conditional short circuit
capacity Icn
Rated voltage DC Conditional short circuit
capacity Icn
UL 508
CSA C22.2 no. 14
05 - 52 A 480Y/277 V 5 kA - -
UL 1077 0.5 - 40 A 480Y/277 V 10 kA - -
CSA C22.2 no. 235 0.5 - 50 A 480Y/277 V 5 kA - -
EN 60934 0.5 - 30 A 240/420 V 4.5 kA 65 V 4.5 kA
GB 17701 - - - - -
Effect of ambient temperature
AC-breaker are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or
higher ambient temperature, use a correction factor from the table below:
Ambient temperature [°C] Correction factor AC version Correction factor DC version
-20 0.78 0.80
-5 0.82 0.87
0 0.83 0.90
+10 0.87 0.95
+23 0.91 1.00
+30 0.95 1.05
+40 1.00 1.10
+50 1.05 1.20
+60 1.11 1.30
Example DC version: Rated current = 10 A; Environmental temperature = 50 °C; --> Correction factor = 1.2; Resulting current = 12 A
5
Thermal-magnetic (TM and AS-line)
AS168XAC4
www.schurter.com /PG20
Circuit Breakers
Ampere-Horsepower
Horsepower
(FLA & LRC Ratings Apply where no HP Rating is given)
Nominal Circuit Voltage, VAC
AS168X-CB Motor Nameplate
110-
120
200208
220-
240
265 277
380-
415
440-
480
Rated Current
(See Note #1)
FLA
Rating
Starting/
LRC Rating
2 pole1 pole
0.5A 0.5A
1A 1A
1.5A 1.5A
2A 2A
3A 3A
4A 4A
5A 5A
6A 6A
7A 7A
8A 8A
9A 9A
10A 10A
12A 12A
13A 13A
15A 15A
16A 16A
18A 18A
20A 20A
23A 23A
25A 25A
27A 27A
30A 30A
AS168X-CB
Nominal Circuit Voltage, VAC
110-120 200208 220-240 380-415 440-480
Rated Current
(See Note #1)
Note #1: For AC motor circuit nameplate FLA loads, AC general-use loades, AC resistance loads
FLA Starting/
3 pole
0.5A 0.5A
1A 1A
1.5A 1.5A 1/2
2A 2A 3/4
3A 3A 1 1/ 2
4A 4A 2
5A 5A 3
6A 6A 3
7A 7A 3
8A 8A 5
9A 9A 5
10A 10A 5
12A 12A 7 1/ 2
13A 13A 7 1/ 2
15A 15A 10
16A 16A 10
18A 18A 10
20A 20A 10
23A 23A 15
25A 25A 15
27A 27A 20
30A 30A 20
Motor Nameplate
Horsepower
(FLA & LRC Ratings Apply where no HP Rating is given)
Rating LRC Rating
10A 1/2
12.5A 3/4
20A 1/2 1/2 1/2 1
25A 3/4 3/4 3/4 1 1/2
32A 1/2 1 1 1 2
32A 1/2 1 1 1/2 2
32A 3/4 1/2 1/2 2 3
46A 3/4 2 2 2 3
46A 1 2 2 2 3
46A 1 2 2 3 5
63.5A 1 1/2 3 3 3 5
63.5A 1 1/2 3 3 3 5
81A 2 3 3 3 7 1/2
81A 2 3 3 5 7 1/2
81A 2 5 5 5 10
81A 3 5 5 5 10
116A 3 5 5 7 1/2 10
116A 3 5 7 1/2 7 1/2 10
145A 3 7 1/2 7 1/2 7 1/2 15
145A 3 7 1/2 7 1/2 10 15
1/10
1/10 1/10 1/10 1/6
12A 1/8 1/6 1/6 1/4
18A 1/10 1/6 1/6 1/4 1/4 1/3 1/3 1/2
24A 1/8 1/4 1/3 1/3 1/3 1/3 1/2 1
30A 1/6 1/3 1/3 1/2 1/2 1/2 3/4 1 1/2
36A 1/4 1/2 1/2 1/2 3/4 3/4 1 2
42A 1/4 1/2 1/2 3/4 1 1 1 1/2 2
48A 1/3 3/4 3/4 1 1 1 2 2
54A 1/3 3/4 1 1 1 1 1/2 2 3
60A 1/2 1 1 1 1/2 1 1/2 2 2 3
72A 1/2 1 1/2 1 1/2 2 2 2 3 3
78A 1/2 1 1/2 1 1/2 2 2 2 3 3
90A 3/4 2 2 2 3 3 3 5
96A 1 2 2 2 3 3 3 5
108A 1 2 2 3 3 3 5 5
120A 1 1/2 3 3 3 3 3 5 5
138A 1 1/2 3 3 3 3 3 5 7 1/2
150A 2 3 3 3 5 5 5 7 1/2
162A 2 3 3 3 5 5 7 1/2 10
180A 2 3 3 5 5 5 7 1/2 10
6
Thermal-magnetic (TM and AS-line)
AS168XAC4
www.schurter.com /PG20
Circuit Breakers
Time-Current-Curves
Version F / Magnetic 3-5 xl
n
Time in Seconds
110 100 1000 x I
n
0,1ms
1ms
10ms
0,1s
1s
10s
100s
1000s
1hr
Multiple of Rated Current In
Reference Temperature +23°
Version G / Magnetic 6-10 xl
n
Time in Seconds
110 100 1000 x I
n
0,1ms
1ms
10ms
0,1s
1s
10s
100s
1000s
1hr
Multiple of Rated Current In
Reference Temperature +23°
Version H / Magnetic 12-20 xl
n
Time in Seconds
110 100 1000 x I
n
0,1ms
1ms
10ms
0,1s
1s
10s
100s
1000s
1hr
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
AS168X-CB|1|DG|200|N|
The characters are placeholders for the correspondingly keys of selections from the key tables.
AS168X-CB| 1 |DG|200|N| = Number ofPoles
Number of Poles Configuration
key
4-pole 4

4420.0408

Mfr. #:
Manufacturer:
Schurter
Description:
Circuit Breakers CBE AS168X-CB4G300
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet