2
G9EN-1 DC Power Relays
Characteristics
Note: The above values are initial values at an ambient temperature of 23°C unless otherwise specified.
*1. The insulation resistance was measured with a 500-VDC megohmmeter.
*2. The impulse withstand voltage was measured with a JEC-212 (1981) standard impulse voltage waveform (1.2 × 50 µs).
*3. The Upper limit of double amplitude: 10 mm P-P
*4. The mechanical endurance was measured at a switching frequency of 3,600 operations/hr.
*5. The electrical endurance was measured at a switching frequency of 60 operations/hr.
*6. The switching performance and interruption performance were measured with a Zener diode and normal diode connected to absorb coil surge. These performances
will be lower if only a normal diode is used.
Engineering Data
Item G9EN-1
Contact voltage drop 0.1 V max. (for a carry current of 60 A)
Operate time 40 ms max.
Release time 20 ms max.
Insulation resistance *1
Between coil and contacts 1,000 MΩ min.
Between contacts of the same polarity 1,000 MΩ min.
Dielectric strength
Between coil and contacts 2,500 VAC 1 min
Between contacts of the same polarity 2,500 VAC 1 min
Impulse withstand voltage *2 4,500 V
Vibration resistance *3
Destruction 5 to 200 to 5 Hz, Acceleration: 44.1 m/s
2
Malfunction 5 to 200 to 5 Hz, Acceleration: 44.1 m/s
2
Shock resistance
Destruction 490 m/s
2
Malfunction
Energized 490 m/s
2
Deenergized 98 m/s
2
Mechanical endurance *4 200,000 min.
Electrical endurance *5 *6 400 VDC, 60 A, 3,000 ops. min.
Short-time carry current 180 A (1 min)
Maximum interruption current *6 500 A at 400 VDC (3 times)
Overload interruption *6 250 A at 400 VDC (200 times min.)
Ambient operating temperature -40 to 85°C (with no icing or condensation)
Ambient operating humidity 5% to 85%
Weight Approx. 140 g
● Maximum Switching Capacity* ● Electrical Endurance
(Switching Performance)*
● Electrical Endurance
(Interruption Performance)*
● Carry Current vs. Energizing Time
●
Must-operate Voltage and Must-release Voltage
Distributions
(Number of Relays × Percentage of Rated Voltage)
● Time Characteristic Distributions
(Number of Contacts × Time (ms))
* The switching performance and interruption performance were measured with a Zener diode and normal diode connected to absorb coil surge. These performanc-
es will be lower if only a normal diode is used.
Switching current (A)
1,000
500
300
100
50
30
10
5
3
1
Switching voltage (V)
30 5010 100 300 500 1,000
Switching current (A)
30 5010 100 300 500 1,000
Operations (×10,000)
10
5
3
1
0.5
0.3
0.1
0.05
0.03
0.01
0.005
0.003
0.001
Operations
1,000
500
300
100
50
30
10
5
3
1
Switching current (A)
30 5010 100 300 500 1,000
Carry current (A)
30 5010 100 300 500 1,000
Energizing time (s)
100,000
10,000
1,000
100
10
1
30
25
20
15
10
5
0
20 40 60 80 100
Percentage of rated voltage (%)
Number of Relays
Must-operate Voltage
Must-release Voltage
30
25
20
15
10
5
0
3 6 9 12 15
Time (ms)
Number of Contacts
Operate time
Release time