W2E250-HJ32-01

AC axial compact fan
sickled blades (S series)
W2E250-HJ32-01
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]
2.0001.8001.6001.4001.2001.0008006004002000
qv[cfm]
1.2001.0008006004002000
p f s[Pa]
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
pfs _E[IN H2O]
0,85
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
0
p f s[Pa]
1
2
3
4
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
115
115
115
115
f
Hz
50
50
50
50
n
min
-1
2600
2570
2505
2435
P
e
W
115
128
137
147
I
A
1.02
1.12
1.20
1.29
qv
m
3
/h
1900
1735
1515
1190
p
fs
Pa
0
40
80
110
U = Supply voltage · f = Frequency · n = Speed · P
e
= Power input · I = Current draw · qv = Air flow · p
fs
= Pressure increase
Item no. 11386-5-9980 · Revision 80549 · Release 2014-04-04 · Page 4 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Measurement: LU-29333
AC axial compact fan
sickled blades (S series)
W2E250-HJ32-01
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]
2.2002.0001.8001.6001.4001.2001.0008006004002000
qv[cfm]
1.2001.0008006004002000
p f s[Pa]
180
175
170
165
160
155
150
145
140
135
130
125
120
115
110
105
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
pfs _E[IN H2O]
0,72
0,7
0,68
0,66
0,64
0,62
0,6
0,58
0,56
0,54
0,52
0,5
0,48
0,46
0,44
0,42
0,4
0,38
0,36
0,34
0,32
0,3
0,28
0,26
0,24
0,22
0,2
0,18
0,16
0,14
0,12
0,1
0,08
0,06
0,04
0,02
0
p f s[Pa]
1
2
3
4
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
115
115
115
115
f
Hz
60
60
60
60
n
min
-1
2850
2760
2620
2445
P
e
W
160
178
185
194
I
A
1.42
1.53
1.60
1.68
qv
m
3
/h
2075
1880
1620
1200
p
fs
Pa
0
40
80
110
U = Supply voltage · f = Frequency · n = Speed · P
e
= Power input · I = Current draw · qv = Air flow · p
fs
= Pressure increase
Item no. 11386-5-9980 · Revision 80549 · Release 2014-04-04 · Page 5 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

W2E250-HJ32-01

Mfr. #:
Manufacturer:
ebm-papst
Description:
AC Fans AC Axial Fan, 280x280x80mm, 115VAC, 1100CFM, 175W, 73dBA, Ball Bearing, Terminal Block
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet