Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on
the module for one 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.
The figure shows the PT-
IQ-1x2-24DC-UT version
Product Features
Surge protection system
Multi-level state monitoring
Collective message about supply and remote module
System supplied via DIN rail bus
Up to 28 protection modules per supply module
Maximum ease of maintenance thanks to the two-piece design
Codable plug
Impedance-neutral disconnection of plug for maintenance purposes
Base element remains an integral part of the installation
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 140.0 GRM
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 91.1 mm
Width 17.7 mm
https://www.phoenixcontact.com/us/products/2800975
09/10/2014Page2/6
Surge protection device-PT-IQ-1X2+F-12DC-UT-2800975
Technical data
Dimensions
Depth 77.5 mm
Horizontal pitch 1 Div.
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Mounting type DIN rail mounting
Type DIN rail module, two-section, divisible
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
12 V
Maximum continuous operating voltage U
C
15 V DC
10 V AC
Nominal current I
N
1000 mA (Up to 45°C)
Operating effective current I
C
at U
C
≤ 1 mA (per system)
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
(8/20) µs (Core-Core)
10 kA
Nominal discharge current I
n
(8/20) µs (Core-Earth)
10 kA
Total surge current (8/20) µs 20 kA
Impulse discharge current (10/350)˽µs, peak value l
imp
2.5 kA
Voltage protection level U
P
(Core-Core)
≤ 65 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
≤ 110 V (C2 - 10 kA)
≤ 35 V (C3 - 25 A)
≤ 40 V (C3 - 50 A)
Voltage protection level U
P
(Core-Earth)
≤ 900 V (C1 - 1 kV/500 A)
≤ 1300 V (C2 - 10 kV / 5 kA)
https://www.phoenixcontact.com/us/products/2800975
09/10/2014Page3/6
Surge protection device-PT-IQ-1X2+F-12DC-UT-2800975
Technical data
Protective circuit
≤ 1200 V (C2 - 10 kA)
≤ 1000 V (C3 - 25 A)
≤ 1300 V (C3 - 100 A)
Voltage protection level U
P
(Core-GND)
≤ 600 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 800 V (C2 - 10 kA)
≤ 700 V (C3 - 25 A)
≤ 800 V (C3 - 100 A)
Voltage protection level U
P
static (core-core)
≤ 41 V (C1 - 1 kV/500 A)
Response time tA (Core-Core) ≤ 1 ns
Response time tA (Core-Earth) ≤ 100 ns
≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 95 kHz)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 600 kHz
Capacity (Core-Earth) 4 nF
Resistance in series 1.2 Ω ±5 %
Surge protection fault message Optical, multi-stage
Max. required back-up fuse 1 A (FF)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Core) C1 (1 kV/500 A)
C2 (10 kV/5 kA)
C2 (10 kA)
C3 - 25 A
C3 (50 A)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C1 (1 kV / 500 A)
C2 (10 kV / 5 kA)
C2 (10 kA)
C3 (25 A)
C3 (50 A)
C3 - 100 A
D1 - 2,5 kA
Surge carrying capacity in acc. with IEC 61643-21 (Core-GND) C1 (1 kV/500 A)
C2 (10 kV/5 kA)
C2 (10 kA)
C3 (25 A)
C3 (50 A)
C3 (100 A)
Pulse reset time tr in acc. with IEC 61643-21 (Core-Core) ≤ 25 ms