H7GP
5
Operation
■ DIP Switch Settings
Set all DIP switches before mounting the Counter to a control panel.
All switches are set toward the display panel before shipping.
H7GP-C/-CD
H7GP-T/-TD
Note: 1. When the setting has been changed, turned power off and
on to continue. The display will show “0” when the power is
turned back on.
2. The decimal point will flash every second when “99999.9 h”
is set.
■ Operating Modes
Nomenclature
Switch Item Function
3 (On right side
from front)
Input mode (note
1)
Display side NPN
Terminal side PNP
4 (On left side
from front)
Counting speed
(note 1)
Display side 30 Hz
Terminal side 5 kHz
Switch Item Function
3 (On right side
from front)
Input mode
(note 1)
Display side NPN
Te r m i n a l s i d e P N P
4 (On left side
from front)
Time range
(note 1)
Display side 99999.9h
(note 2)
Terminal side 99 h 59 min
59 s
0
0.0h
999999
Total Counters Time Counters
Reset input
Count input
Display
Start input
Display
Reset input
99999.9 h
(see note)
Note: The count value will return to "0" when "999999" is
exceeded.
The display and output are turned OFF when the power
supply turns OFF, but the count value is stored internally.
Note: Display values are shown for full scale set to 99999.9 h.
The count value will return to "0" when "99999.9" is
exceeded.
The display and output are turned OFF when the power
supply turns OFF, but the count value is stored internally.
1. Reset Key
Resets the count value, but will not operate while
the keys are protected.
2. Key Protection Indicator
Lit while the keys are protected. (Reset Key is
disabled.).
3. NPN/PNP DIP Switch
(Count or start with reset)
When the setting has been changed, turned power
off and on to continue. The display will show "0"
when the power is turned back on. See below for
details.
4. Counting Speed DIP Switch (H7GP-C)
Time Range DIP Switch (H7GP-T)
When the setting has been changed, turned power
off and on to continue. The display will show "0"
when the power is turned back on. Refer to DIP
Switch Setting for details.
4
2
1
3