Power supply, with protective coating-QUINT-PS/1AC/24DC/ 5/
CO-2320908
Technical data
Connection data, output
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Connection data for signaling
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 12
Screw thread M3
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Shock 30g in each direction, according to IEC 60068-2-27
Noise emission EN 55011 (EN 55022)
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CSA
Standards/regulations EN 61000-4-3
EN 61000-4-4
EN61000-4-6
Standard – Electrical equipment of machines EN 60204-1
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Equipment safety BG (design tested)
Shipbuilding approval Germanischer Lloyd (EMC 2)
UL approvals UL/C-UL listed UL 508