2701298

IB IL 24 PWR IN/R-XC-PAC
8499_en_01 PHOENIX CONTACT 7
7 Internal circuit diagram
Figure 2 Internal wiring of the terminal points
Key:
UL
US
UM
+24 V (U )
M
+24 V (U )
S
Local bus
U
L+
1
U
ANA
U
L-
7,5 V
5 V
24 V
7,5 V
LED
Electrically isolated area
Power supply unit
Diode
Reference potential GND (24 V supply)
Explanation for other used symbols has been
provided in the IL SYS INST UM E user man-
ual.
1
IB IL 24 PWR IN/R-XC-PAC
8499_en_01 PHOENIX CONTACT 8
8 Terminal point assignment
Figure 3 Terminal point assignment
1.1 2.1
1.2 2.2
1.3 2.3
1.4 2.4
1.1
1.2
1.3
1.4
2.1
2.3
2.4
2.2
Terminal point Designation Assignment
Connector 1 Not used
Connector 2 Not used
Connector 3 Voltage supply for generating the communications power and analog voltage
1.1 / 2.1 Not used
1.2 / 2.2 24VDC For generating U
L
and U
ANA
1.3 / 2.3 GND Ground Ground of the 24 V supply
1.4 / 2.4 FE Functional earth
ground
Functional earth ground of the power terminal and, therefore,
of the Inline station.
The contacts are directly connected to the potential jumper
and the FE spring on the bottom of the housing.
Connector 4 Voltage supply for the main circuit and segment circuit
1.1 / 2.1 24VDC U
S
24 V supply for segment circuit
1.2 / 2.2 24VDC U
M
24 V supply for main circuit
1.3 / 2.3 GND Reference potential of
the I/O supply
The reference potential is routed directly to the potential
jumper and simultaneously functions as reference ground for
the main and segment supplies.
1.4 / 2.4 FE Functional earth
ground
Functional earth ground of the power terminal and, therefore,
of the Inline station.
The contacts are directly connected to the potential jumper
and the FE spring on the bottom of the housing.
Functional earth ground is only used to dis-
charge interference.
NOTE: Electronics may be damaged when
overloaded
Ensure that the maximum permissible current
of 8A flowing through potential jumpers U
M
and U
S
(total current) is not exceeded.
NOTE: Malfunction
Connect the power terminal to the functional
earth ground (FE) via one of the FE connec-
tions of connector 3 or connector 4. To do so,
connect the corresponding contact to a
grounding terminal block.
IB IL 24 PWR IN/R-XC-PAC
8499_en_01 9
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
24 V segment supply/24 V main supply
The segment supply and main supply must have the same
reference potential. Therefore, an electrically isolated volt-
age area on the I/O side cannot be created.
The main supply and the segment supply are protected
against polarity reversal and surge voltage.
24 V segment supply
You can provide the segment voltage at this terminal or one
of the supply terminals.
There are several ways of providing the segment voltage at
the terminal (connector 4):
1. The segment voltage can be supplied separately at ter-
minal points 1.1 (or 2.1) and 1.3 (or 2.3) (GND) of the
power connector.
2. Connections 1.1 (or 2.1) and 1.2 (or 2.2) can be jump-
ered to tap the supply for the segment circuit from the
main circuit.
3. A switch can be inserted between terminal points 1.1 (or
2.1) and 1.2 (or 2.2) to create a switched segment cir-
cuit (e.g., an emergency stop circuit).
24 V supply for generating U
L
and U
ANA
The 24 V supply has protection against polarity reversal and
surge voltage. These protective elements are only used to
protect the power supply unit.
9 Local diagnostic indicators
Figure 4 Local diagnostic indicators
Function identification
Black
10 Connection example
Figure 5 Typical connection of the supply voltage
NOTE: Module can become damaged
The main supply and segment supply do not
have short-circuit protection.
The user must provide short-circuit protec-
tion. Measure the rating of the fuse connected
upstream such that the maximum permissible
load current is not exceeded.
NOTE: Module can become damaged
The 24 V supply does not have short-circuit
protection.
The user must provide short-circuit protec-
tion. Measure the rating of the fuse connected
upstream such that the maximum permissible
load current is not exceeded.
LED Color Meaning
UL Green 7.5 V communications power
US Green 24 V supply for segment circuit
UM Green 24 V supply for main circuit
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
+
-
24VDC
(U
BK
)
+
24VDC
(U
S
)
-
24VDC
(U
M
)
+
-

2701298

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules IB IL 24 PWR IN/R XC-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet