Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...
www.e-t-a.de
1708 1
1
Description
Typical applications
Technical data
Single, two and three pole magnetic and hydraulic-magnetic circuit
breakers with trip-free mechanism and toggle actuation. A choice of
fast magnetic only or hydraulically delayed switching characteristics
(S-type MO or HM CBE to EN 60934) ensures suitability for a wide
range of applications. Featuring a combi-foot design for symmetric rail
mounting. Low temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934).
Power supplies, control equipment, communication systems, EDP
systems.
8340-T...
single pole three pole
For further details please see chapter: Technical Information
Voltage rating 3 AC 415V; AC 240V (50/60Hz); DC 80V
(higher DC voltages to special order)
Current rating range 0.02...50 A DC
0.02...30 A AC
Auxiliary circuit 1 A, AC 240 V/DC 65 V; 0.5 A DC 80 V
Typical life 3 AC 415 V AC 240 V:
0.02...30 A 6,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, resistive
WDC 80 V: 0.02...25 A 6,000 operations at 1 x I
N
, inductive
0.02...30 A 10,000 operations at 1 x I
N
, resistive
40 + 50 A 6,000 operations at 1 x I
N
, resistive
Ambient temperature -40...+85 °C (-40...+185 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area test voltage AC 3,000 V
Line to Load test voltage AC 1,500 V
pole to pole
(2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity 6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity I
N
0.02...20 A 25...30 A
(UL 1077) AC: 1-pole AC 250 V/3,500A AC 250 V/3,500A
2-pole AC 250 V/3,500A AC 250 V/5,000A
3-pole 3AC 250V/3,500A 3AC250V/5,000A
DC: 1-pole 0.02...50 A DC 80 V/3,500 A
2-pole 0.02...30 A DC 80 V/3500 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP20
Vibration
with toggle down: 10 g at 0.9 I
N
directions 1, 2, 3, 4, 5: 10 g at 1 x I
N
with curves F1, F2: 10 g at 0.8 x I
N
in all planes.
(57-2000 Hz) ± 0.76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
directions 1, 2, 3, 4, 5: 100 g (11 ms) at 1 x I
N
direction 6: 100 g (11 ms) at 0.8 x I
N
with curves F1, F2: 100 g (11 ms) at 0.8 x I
N
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass approx. 98 g per pole
Standard current ratings and typical internal resistance values
Current
rating (A)
Internal resistance values (Ω) per pole
F1 F2 K1, M1, T1 K2, M2, T2
0,02 1 493 953 2 669 2 457
0,05 276 152 452 376
0,1 58 37 100 94
0,25 8,2 6,0 15,5 14,7
0,5 2,3 1,47 3,9 3,2
0,75 0,98 0,63 1,65 1,56
1 0,58 0,35 0,95 0,90
2 0,145 0,096 0,26 0,20
2,5 0,096 0,061 0,15 0,15
3 0,065 0,048 0,10 0,10
5 0,025 < 0,02 0,042 0,040
6 < 0,02 < 0,02 0,029 0,028
8 < 0,02 < 0,02 < 0,02 < 0,02
10 < 0,02 < 0,02 < 0,02 < 0,02
12 < 0,02 < 0,02 < 0,02 < 0,02
15 < 0,02 < 0,02 < 0,02 < 0,02
16 < 0,02 < 0,02 < 0,02 < 0,02
20 < 0,02 < 0,02 < 0,02 < 0,02
25 < 0,02 < 0,02 < 0,02 < 0,02
30 < 0,02 < 0,02 < 0,02 < 0,02
40 < 0,01 - < 0,01 -
50 < 0,01 - < 0,01 -