Designed to IEC Standard
Axial Lead and Cartridge Fuses
5 x 20 mm Time Lag Fuse (SIo-Blo
®
Fuse) 219 Series
404
www.littelfuse.com
• Designed to International (IEC) Standards for use globally.
• Meets the IEC 60127-2, Sheet 6 specification for Time Lag Fuses.
• Available in Cartridge and Axial Lead Format.
• Available in ratings of 1.0 to 6.3 amperes.
• Enhanced Breaking Capacity, medium I
2
t
ELECTRICAL CHARACTERISTICS:
% of Ampere Opening
Rating Time
150% 60 minutes, Minimum
210% 2 minutes, Maximum
275% 0.6 sec., Min.; 10 sec. Max
400% .15 sec., Min.; 3 sec. Max
1000% 0.02 sec., Min.; 0.3 sec. Max.
AGENCY APPROVALS: Sheet 6 IEC 60127: SEMKO, BSI, METI, CCC, K Mark
and VDE approved 1A-6.3A. Recognized 1A to 6.3A under the components pro-
gram of Underwriters Laboratories and recognized by CSA. METI A 1A to 6.3A.
INTERRUPTING RATINGS: 150 amperes @ 250VAC, unity power factor
PACKAGING: For Axial Leads add packaging suffix XE.
ORDERING INFORMATION:
Nominal Nominal Nominal
Catalog Ampere Voltage Resistance Melting I
2
t
Number Rating Rating Cold Ohms A
2
Sec
0219 001. 1 250 0.055 3.33
0219 1.25 1.25 250 0.042 5.80
0219 01.6 1.6 250 0.032 10.61
0219 002. 2 250 0.029 14.80
0219 02.5 2.5 250 0.022 23.85
0219 3.15 3.15 250 0.017 39.20
0219 004. 4 250 0.013 70.95
0219 005. 5 250 0.010 114.0
0219 06.3 6.3 250 0.0075 204.0