241 03/01
3-Line Filters
B84143-G*-R112
B84143-G*-R110
for Converters and Power Electronics
Technical data
Characteristics and ordering codes
Compilation of ordering code
Replace the asterisk * by the code number for the required version:
0 = 480 / 275 V
2 = 520 / 300 V
1) At rated operation
Rated voltage V
R
480/275 V~, 50/60 Hz (type -R110)
520/300 V~, 50/60 Hz (type -R112)
Rated current I
R
Referred to 40 °C ambient temperature
Test voltage V
P
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability 1,5 · I
R
for 3 min per hour or
2,5 · I
R
for 30 s per hour
Leakage current I
leak
at 480 V~, 50 Hz
Climatic category 25/100/21 (– 25
°C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
I
R
A
Terminal cross section I
leak
R
typ
mΩ
Approx.
weight
kg
Ordering code
line side:
terminal
blocks
mm
2
load side:
litz wires
mm
2
typ.
1)
mA
84 1,5
< 6 40 1,3 B84143-G8-R11*
20 4 2,5
< 6 10 1,3 B84143-G20-R11*
36 6 6,0
< 16 5,2 2,8 B84143-G36-R11*
50 16 10
< 16 2,4 3,3 B84143-G50-R11*
66 25 16
< 16 1,8 4,4 B84143-G66-R11*
90 25 25
< 16 1,2 4,9 B84143-G90-R11*
120 50 35
< 16 1,0 7,5 B84143-G120-R11*
150 50 35
< 16 0,7 8,0 B84143-G150-R11*
220 95 70
< 16 0,4 11,5 B84143-G220-R11*