SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT (20.5CFM)
RATED POWER (convection)
Note.7
CURRENT RANGE (20.5CFM)
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.6
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
Note.9
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
AC CURRENT (Typ.)
1800ms, 30ms/230VAC 3500ms, 30ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
16ms/230VAC/115VAC at full load
47 ~ 63Hz
PF>0.93/230VAC PF>0.98/115VAC at full load
1.8A/115VAC 0.9A/230VAC
COLD START 35A/115VAC 70A/230VAC
105 ~ 135% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
CH1: 5.75 ~ 6.75V
TSW2: Shut down o/p voltage, re-power on to recover
TSW1: Shut down o/p voltage, recovers automatically after temperature goes down
ANSI/AAMI ES60601-1, TUV EN60601-1 approved
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
160W Triple Output Medical Type
RPT-160 series
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
5"x3" compact size
Free air convection for 100W and 145W with 20.5 CFM forced air
Medical safety approved (2 x MOPP between primary to secondary)
With power good and fail signal output
No load power consumption under 0.75W by PS-ON control (G model)
Standby 5V@0.8A with fan, @0.6A without fan (G model)
Suitable for BF application with appropriate system consideration
3 years warranty
■
Features :
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
SAFETY &
EMC
(Note 4)
PROTECTION
ENVIRONMENT
CURRENT RANGE (convection)
RIPPLE & NOISE (max.)
Note.2
RATED POWER (20.5CFM)
Note.8
VOLTAGE TOLERANCE
Note.3
POWER GOOD / POWER FAIL
Power on: PS-ON = "Hi" or " > 2 ~ 5V" ; Power off: PS-ON = "Low" or " < 0 ~ 0.5V"
500ms>PG>10ms PF>1ms
FUNCTION
Compliance to EN55011 (CISPR11), EN55032 (CISPR32) Class B, EN61000-3-2,-3
MTBF
DIMENSIONOTHERS
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, EN61204-3, medical level, criteria A
191.4K hrs min. MIL-HDBK-217F (25 )℃
127*76.2*34.6mm (L*W*H)
PACKING
0.33Kg; 36pcs/12.9Kg/0.79CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
5. HS1,HS2 & HS3 can not be shorted.
6. Derating may be needed under low input voltages. Please check the derating curve for more details.
7. The rated power includes 5Vsb @ 0.6A.
8. The rated power includes 5Vsb @ 0.8A.
9. Touch current was measured from primary input to DC output.
84%
CH1 CH1 CH1 CH1OUTPUT NUMBER
RPT -160A□
5V
14A
0.6 ~ 9A
0.6 ~ 14A
14A
0.6 ~ 9A
0.6 ~ 14A
98.6W
145W
100mVp-p
CH1:5 ~ 5.5V
±2.0%
±0.5%
±1.5%
RPT -160B□ RPT -160C□ RPT -160D□
12V
CH2 CH2 CH2 CH2
-5V
CH3 CH3 CH3 CH3
12V -12V 15V 12V-15V 24V5V 5V 5V
5.5A
0.2 ~ 3.8A
0.2 ~ 5.5A
5A
0.2 ~ 3.4A
0.2 ~ 5A
1A
0.1 ~ 0.6A
0.1 ~ 1A
1A
0.1 ~ 0.8A
0.1 ~ 1A
3.6A 5A
0.1 ~ 2.6A 0.2 ~ 2.6A
0.1 ~ 3.6A 0.2 ~ 5A
1A 1.2A
0.1 ~ 0.8A
0.15 ~ 1A
0.1 ~ 1A
0.15 ~ 1.2A
14A 11A
0.6 ~ 9A 0.3 ~ 8A
0.6 ~ 14A 0.3 ~ 11A
98.4W
146W
99W 98.2W
143W 147.8W
120mVp-p 120mVp-p 100mVp-p 120mVp-p 120mVp-p 150mVp-p 120mVp-p
150mVp-p
200mVp-p
100mVp-p
100mVp-p
±5.0% -5,+7% ±5.0% -4,+5% ±4.0% ±5.0%±8.0% +7,-5%
±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%±1.0% ±1.0%
±3.0% -5,+6% ±3.0% -4,+5% ±3.0% ±3.0%±8.0% -3,+4%
±2.0% ±2.0% ±2.0%
±0.5%
±1.5%
±0.5% ±0.5%
±2.0% ±1.5%
84% 83% 83%
5V STANDBY (G model)
5VSB : 5V@0.6A without fan, 0.8A with fan 20.5CFM ; tolerance 2%, ripple : 50mVp-p(max.)±
RPT 160A
G
consumption < 0.75 W
G: With 5Vsb & no load power
Blank: Basic function (without 5Vsb)
PS-ON INPUT SIGNAL (G model)
EMC IMMUNITY
EMC EMISSION
Earth leakage current < 200 A/264VAC , Touch current < 100 A/264VACμμ
ISOLATION LEVEL
Primary-Secondary: 2xMOPP, Primary-Earth:1xMOPP, Secondary-Earth:1xMOPP
EN 60601-1
IEC 60601-1
8
File Name:RPT-160-SPEC 2017-07-14