SUINT3000RTXL2U

SmartOnline 208/240, 230V 3kVA 2.5kW Double-
Conversion UPS, 2U Rack/Tower, Extended Run,
Network Card Options, USB, DB9 Serial
MODEL NUMBER: SUINT3000RTXL2U
Description
3000VA / 3kVA / 2500 watt on-line, double-conversion UPS system for critical server, network and
telecommunications equipment. 2U rackmount form factor with an installed depth of only 66cm (26
inches). Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack
compatible) and BP72V18-2US (multi-pack compatible) external battery packs. Full time sine wave
200/208/220/230/240V output with +/-2% voltage regulation. Uninterruptible Power Supply (UPS) actively
converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC
output. Operates continuously without using battery power during brownouts to 120V and overvoltages to
288V. Up to 97% efficiency in optional economy mode saves BTU heat output and energy costs. C20 inlet
accepts a wide variety of optional cordsets. C19 and C13 output receptacles. Network-grade AC surge
and noise suppression. Zero transfer time between AC and battery operation. Network management
interfaces include USB port, DB9 serial port and slot for network management card options. Built-in DB9
port offers both enhanced RS-232 enabled monitoring data, plus contact closure monitoring ability. HID-
compliant USB interface enables integration with built-in power management and auto shutdown features
of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test
data and mains power conditions via all network interfaces. PowerAlert monitoring software is available
via free download. Emergency Power Off (EPO) interface. Integrated two bank PDU switching supports
automated load shedding and remote-reboot of connected equipment. Multi-stage metered current
monitoring and battery charge status LEDs. Mains power and voltage regulation LEDs. Audible Alarm.
Self-test. Fault-tolerant auto-bypass mode. LED display panel easily rotates for better viewing in
rackmount or tower configurations. Includes 4 post rackmount installation accessories. 2-9USTAND tower
kit and 2POSTRMKITWM two post rackmount hardware accessories available. Field replaceable, hot
swappable internal batteries and external battery packs.
Features
Highlights
3000VA / 3kVA / 2500 watt on-
line double-conversion 2U rack /
tower UPS
200/208/220/230/240V 50/60Hz
output; High efficiency economy
mode option
Expandable runtime; Hot-swap
batteries
USB, RS232 & EPO ports;
Network Management Card
Options
Front panel status LEDs with
detailed load and battery
metering
2 independently switchable
output load banks
C20 inlet; C13 & C19 outlets, 2
C13 to C14 & 1 C19 to C20
power cables included
Package Includes
SUINT3000RTXL2U UPS
System
4 post rackmount installation
brackets
C19 to C20 power cable
USB, Serial and EPO cabling
Owner's manual with warranty
information
1 / 7
SmartOnline high-performance UPS system is ideal for critical voice, data, medical and industrial
network applications
Optional economy-mode operation with 97% efficiency for reduced power consumption and cooler
operation
Economy mode is schedulable via PowerAlert UPS management software for daily or weekly hours of
operation to enable precision output during peak operating hours and high efficiency, low BTU emission
operation during off-peak times
Maintains continuous operation through blackouts, voltage fluctuations
On-line, double-conversion mode provides perfectly regulated sine wave output within 2% of
200/208/220/230/240V (user selectable) with zero transfer time
Supports operation at 50/60Hz (auto-sensing) with the ability for full-time frequency conversion from 50
to 60Hz or 60 to 50Hz (frequency conversion de-rates UPS capacity by 20%)
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve
power problems not addressed by other UPS types
Corrects line voltage conditions as low as 120V and as high as 288V to within 2% of selected nominal
voltage
Standard internal battery set offers 15 minutes runtime at half load (1250W) and 6 minutes at full load
(2500W)
Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack
compatible) and BP72V18-2US (multi-pack compatible) external battery packs
Intelligent battery management system extends battery life
Compact rackmount form factor installs using only 2 rack spaces (2U) with a depth of only 66cm / 26
inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITWM enables 2 post rackmount installation
Optional 2-9USTAND accessory enables upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure
and slot for network management card options
Compatible Tripp Lite UPS management card options TLNETCARD, WEBCARDLX and
SNMPWEBCARD support a wide variety of UPS control and monitoring capabilities
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from www.tripplite.com/poweralert
Built-in Emergency Power Off (EPO) interface with cable
C20 inlet accepts a wide variety of user supplied input cordsets
C19 & C13 output receptacles
Includes 2 C13 to C14 and 1 C19 to C20 power cables
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot
of individual load banks (each bank has 4 C13 outlets)
2 / 7
Specifications
Front panel LEDs offer current monitoring and battery charge level information
Network grade AC surge suppression
Optional PDUBHV20 bypass PDU enables hot-swappable UPS replacement with no disruption to
connected equipment
Field replaceable, hot swappable internal batteries and external battery packs
OVERVIEW
UPC Code 037332149183
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2500
Output kW Capacity (kW) 2.5
Output Capacity Details Max output is reduced to 2400W at 200V, 208V and 220V nominal settings
OVERLOAD CAPACITY: Supports inverter operation up to 100% load continuously, 120% for 30 seconds, 150% for
10 seconds and >150% for 0.1 seconds before switching to BYPASS (when bypass input voltage and frequency are
WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).
Power Factor 0,8
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
200V; 208V; 220V; 230V; 240V
Nominal Voltage Details 230V default
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start. Frequency conversion from 60
to 50 Hz -or- 50 to 60 Hz supported. Output capacity de-rates by 20% during frequency conversion operation.
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
-12%, + 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles (8) C13; (2) C19
Included Output Power Cables Includes 2 C13 to C14 and 1 C19 to C20 power cables
Load Management Receptacles Two switchable 4 C13 outlet load banks
Hot-Swap PDU options PDUBHV20 (2U / 6 C13, 2 C19 outlets)
Output AC Waveform (AC Mode) Sine wave
3 / 7

SUINT3000RTXL2U

Mfr. #:
Manufacturer:
Tripp Lite
Description:
UPS - Uninterruptible Power Supplies Tripp Lite 3000VA 2500W UPS International Smart Online Rackmount 208-240V
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet