FCD Series
118
FCD Series
3-phase Delta External Power Line Filter for Frequency Converters
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please go to
te.com/help
corcom.com
• Suitable to meet the latest EMC standards
• Insulated safety terminals
• Suitable for EMC troubleshooting in the field
• Very high attenuation
• High insertion loss
• BS models optimized for very high insertion loss
• BS models suitable for infeed/regenerative (ER)
applications
• Touch safe terminals provide easy connections
and prevent inadvertent contact for safety in the
most demanding applications
Ordering Information
150 FCD 10 BS -95
Terminal Block Option
-95 – 95mm terminal block
available on 150A only
omit for standard terminals
F
ilter Type
B – Single stage
BS – High performance
Single stage.
Omit for dual stage
I
nput / Output Style
10 – Terminal Block
F
CD Series
Current Rating
6, 12, 16, 25, 36, 50, 80, 110,
150, 180 or 230A
Specifications
Electrical Schematics
UL Recognized
6FCD10
PE PE
6FCD10
Maximum leakage current
voltage drop to virtual N to PE/V:
6FCD10: .26 mA/V
12 & 16FCD10: .45 mA/V
25, 36 & 50FCD10: .52 mA/V
12 & 16FCD10B: .46 mA/V
25& 36FCD10B: .52 mA/V
50FCD10B: .57 mA/V
80 & 110FCD10B: .62 mA/V
150FCD10B: .63 mA/V
180 & 230FCD10B: .92 mA/V
FCD10BS: 3.25 mA/V
Hipot rating (one minute):
Line to Ground: 2250 VDC
Line to Line: 1450 VDC
Rated Voltage (max):
Phase to Phase: 480 VAC
Phase to Neutral
/ Gro
und: 277 VAC
Operating Frequency: 50/60 Hz
Rated Current: 6 to 230A
Operating Ambient Temperature Range
(at rated current I
r
): -10°C to +40°C
In an ambient temperature (T
a
) higher than +40°C
the maximum operating current (I
o
) is calculated as
follows: I
o
= I
r
(85-Ta)/45