Digital I/O Slave Units with e-CON Connectors CRT1-@D16S(-1)/@D32S(-1)/@D16SH(-1)/@D32SH(-1) 47
Output Section Specifications
● Sixteen-point Output Unit
● Thirty-two-point Output Unit
Item Specification
Model CRT1-OD16S CRT1-OD16S-1 CRT1-OD16SH CRT1-OD16SH-1
I/O capacity 16 outputs
Internal I/O common NPN PNP NPN PNP
Rated output current 0.5 A/output, 4 A/common
Residual voltage
1.2 V max. (0.5 A DC, between each
output terminal and the G terminal)
1.2 V max. (0.5 A DC, between each
output terminal and the V terminal)
1.2 V max. (0.5 A DC, between each
output terminal and the G terminal)
1.2 V max. (0.5 A DC, between each
output terminal and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Load short-circuit detection --- Supported.
Disconnection detection --- Operates at 3 mA/point max. (Does not operate at over 3 mA.)
Number of circuits per common
16 outputs/common
Isolation method Photocoupler
Output indicators LED (yellow)
Installation DIN Track
Power supply type Multi-power supply
Current supplied to output devices
100 mA/output
Communications power supply
current consumption
40 mA max. for 24-VDC power supply voltage
60 mA max. for 14-VDC power supply voltage
40 mA max. for 24-VDC power supply voltage
65 mA max. for 14-VDC power supply voltage
I/O power supply current
consumption
20 mA max. for 24-VDC power supply voltage
15 mA max. for 24-VDC power
supply voltage
60 mA max. for 24-VDC power
supply voltage
Output handling for
communications errors
Select either hold or clear from CX-Integrator.
Weight 110 g max.
Item Specification
Model CRT1-OD32S CRT1-OD32S-1 CRT1-OD32SH CRT1-OD32SH-1
I/O capacity 32 outputs
Internal I/O common NPN PNP NPN PNP
Rated output current 0.5 A/output, 4 A/common
Residual voltage
1.2 V max. (0.5 A DC, between each
output terminal and the G terminal)
1.2 V max. (0.5 A DC, between each
output terminal and the V terminal)
1.2 V max. (0.5 A DC, between each
output terminal and the G terminal)
1.2 V max. (0.5 A DC, between each
output terminal and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Load short-circuit detection --- Supported.
Disconnection detection --- Operates at 3 mA/point max. (Does not operate at over 3 mA.)
Number of circuits per common
16 outputs/common
Isolation method Photocoupler
Output indicators LED (yellow)
Installation DIN Track
Power supply type Multi-power supply
Current supplied to output devices
100 mA/output
Communications power supply
current consumption
50 mA max. for 24-VDC power supply voltage
80 mA max. for 14-VDC power supply voltage
50 mA max. for 24-VDC power supply voltage
90 mA max. for 14-VDC power supply voltage
I/O power supply current
consumption
15 mA max. for 24-VDC power supply voltage
60 mA max. for 24-VDC power
supply voltage
Output handling for
communications errors
Select either hold or clear from CX-Integrator.
Weight 170 g max.