ADM2490E
Rev. A | Page 13 of 16
THERMAL SHUTDOWN
The ADM2490E contains thermal-shutdown circuitry that protects
the part from excessive power dissipation during fault conditions.
Shorting the driver outputs to a low impedance source can result in
high driver currents. The thermal sensing circuitry detects the
increase in die temperature under this condition and disables
the driver outputs. This circuitry is designed to disable the driver
outputs when a die temperature of 150°C is reached. As the device
cools, the drivers are re-enabled at a temperature of 140°C.
FAIL-SAFE RECEIVER INPUTS
The receiver inputs include a fail-safe feature that guarantees a
logic high on the RxD pin when the A and B inputs are floating
or open-circuited.
MAGNETIC FIELD IMMUNITY
The limitation on the magnetic field immunity of the iCoupler
is set by the condition in which an induced voltage in the receiv-
ing coil of the transformer is large enough to either falsely set or
reset the decoder. The following analysis defines the conditions
under which this may occur. The 3 V operating condition of
the ADM2490E is examined because it represents the most
susceptible mode of operation.
The pulses at the transformer output have an amplitude greater
than 1 V. The decoder has a sensing threshold of about 0.5 V,
thus establishing a 0.5 V margin in which induced voltages can
be tolerated.
The voltage induced across the receiving coil is given by
Nnr
dt
dβ
V
n
,,2,1;
2
K=π
⎟
⎠
⎞
⎜
⎝
⎛
−
=
∑
where:
β is the magnetic flux density (gauss).
N is the number of turns in the receiving coil.
r
n
is the radius of the n
th
turn in the receiving coil (cm).
Given the geometry of the receiving coil and an imposed
requirement that the induced voltage is, at most, 50% of the
0.5 V margin at the decoder, a maximum allowable magnetic
field can be determined using Figure 22.
MAGNETIC FIELD FREQUENCY (Hz)
1k 10k 100k 100M1M 10M
100
10
1
0.1
0.01
0.001
MAXIMUM ALLOWABLE MAGNETIC
FLUX DENSITY (kGAUSS)
5889-010
Figure 22. Maximum Allowable External Magnetic Flux Density
For example, at a magnetic field frequency of 1 MHz, the
maximum allowable magnetic field of 0.2 kgauss induces a
voltage of 0.25 V at the receiving coil. This is about 50% of the
sensing threshold and does not cause a faulty output transition.
Similarly, if such an event occurs during a transmitted pulse and
is the worst-case polarity, it reduces the received pulse from
>1.0 V to 0.75 V, still well above the 0.5 V sensing threshold
of the decoder.
Figure 23 shows the magnetic flux density values in terms of
more familiar quantities, such as maximum allowable current
flow at given distances away from the ADM2490E transformers.
MAGNETIC FIELD FREQUENCY (Hz)
1k 10k 100k 100M1M 10M
DISTANCE = 1m
DISTANCE = 100mm
DISTANCE = 5mm
1000
100
0.1
1
10
0.01
MAXIMUM ALLOWABLE CURRENT (kA)
05889-011
Figure 23. Maximum Allowable Current for
Various Current-to-ADM2490E Spacings
With combinations of strong magnetic field and high frequency,
any loops formed by PCB traces can induce error voltages large
enough to trigger the thresholds of succeeding circuitry. Care
should be taken in the layout of such traces to avoid this
possibility.