88896202

21 mm
-
2 or 4 Relays RTMA4 Part number 88896202
Miniature plug-in timer (21 x 27 mm)
Function A : Delay on energisation
Multi
-range 0.1 s to 10 h
Excellent noise resistance
Relay output, 2 or 4 changeover contacts
Part numbers
Specifications
Type
Functions
Relay outputs
Nominal rating
Absorbed power (W)
88 896 202
RTMA4
A
4 timed changeover
5 A AC
1,2
Timing ranges
0,1→1s
1→10s
0,1→1min
1→10min
0,1→1h
1→10h
Display precision
-
0 % / + 10 % at 25 °C of full scale, according to CEI/EN61812
Repetition accuracy (with constant parameters)
±
0,5 %
Drift Temperature
±
0,05 %/ °C
Drift Voltage
±
0,2 %/V
Maximum reset time by de
-
energisation during timed delay
50 ms
Maximum reset time by de
-
energisation after timing
250 ms
Operating range
±
15 % of supply (AC)
±
10 % of supply (DC)
Frequency (Hz)
50/60 Hz
±
1 Hz
Immunity from micro power cuts : typical
< 5 ms
Ripple
±
10 % (DC)
Operating factor
100 %
Maximum power rating (resistive)
1250 VA / 120 W
Minimum current
100 mA
Maximum breaking voltage
250 V AC
Type of contacts
AgNi
Max. permitted number of operations at 1 max 250 V AC
resistive per hour
600
Electrical life at I max. 250 V AC resistive (number of
operations)
10
5
Mechanical life (operations)
10
7
Breakdown voltage conforming to IEC/EN 61812
-1 and
60601-1
2 kV at 1 mA / 1 min / 50 Hz
Display of output state by LED
Green : power on
yellow : output on
Conformity to standards
CEI/EN61812
-
1, CEI/EN60601
-
1, EN50081
-
2, EN61000
-6-
2, CEI/EN60601
-1-
2, Directives BT (73/23/CEE + 93/68/CEE (CE marking) ) + CEM
(89/336/CEE)
Approvals
UL
-
cUL
Temperature limits use (°C)
-
20→+60
Temperature limits stored (°C)
-
40→+70
Insulation coordination (IEC/EN 60664
-1)
4 kV / surge category 3
Degree of protection IEC 60529
IP 50 (casing)
Vibration resistance
acc. to IEC/EN 60068
-2-6
f=10→55Hz
A = 0,35 mm
Relative humidity (no condensation)
95 % max (CEI 60068
-2-3)
Electromagnetic compatibility (EMC)
Class 2 according to EN61812
-1/A11
Immunity to electrostatic discharges acc.
IEC/EN 61000
-4-
2
Level III (Air 8 K : contact 6kV)
Immunity to radiated, radio
-frequency, electromagnetic
field acc. IEC/EN 61000
-4-3
Level III (10 V/m : 26 M Hz to 1 G Hz / 900 M Hz)
Immunity to rapid transient bursts acc. to IEC/EN 61000
-4-
4
Level III (Direct 2 kV : coupled 1kV)
Immunity to radio frequency in common mode acc. to
IEC/EN 61000
-4-6
Level III (10 V (rms) : 0,15 M Hz to 80 Mhz)
Immunity to shock waves according to IEC/EN 61000
-4-5
AC : level III (common mode 2 kV, differential mode : 1 kV
DC : MC/MD : 0,5 kV
Immunity to voltage dips and breaks acc. to IEC/EN 61000
-
4-11
30 % / 10 ms
60 % / 100 ms / 1 s
> 95 % 5 s
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com
Mains
-
borne and radiated emissions acc. to EN 55022
(CISPR22), EN55011 (CISPR11)
Class B
Housing material
Self-extinguishing
Weight (g)
55
Dimensions (mm)
RTMA2 / RTMA4
Dimensions (mm)
Base for DIN rail mounting
RTMA4 - 26 532 706
Dimensions (mm)
Spring clips for terminal base
26 532 702
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com
Dimensions (mm)
Spring clips for P.C.B. base
26 532 704
Dimensions (mm)
PCB base RTMA4 - 26 532 708
Curves
RTMA4
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com

88896202

Mfr. #:
Manufacturer:
Crouzet
Description:
Timers 4PDT 24VDC RTMA4 TIMER
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet