530-K-1-02-SI-125A

High Performance Thermal-Magnetic Circuit Breakers 410/520/530-...
www.e-t-a.de
1646 1
1
Description
Typical applications
Interrupting capacity to IEC 60947/EN 60947
Approvals
Technical data
Single, double and three pole high performance thermal-magnetic
circuit breakers with tease-free, trip-free, snap action mechanism and
toggle actuation (S-type TM CBE to EN 60 934; also to EN 60 947).
Designed for rail, panel or surface mounting. Available with a choice
of characteristic curves and optional auxiliary contacts.
Motors, generators, transformers, thyristors and silicon rectifiers.
410-... 530-...
Voltage rating AC 240 V; 3 AC 415 V; 3 AC 500 V
DC 110 V
Current rating range
curves 01, 02, 04, 05: 10...125 A (EN 60947)
curves B3, C3, 01: 7...100 A (EN 60898)
Auxiliary circuit 6 A, AC 240 V or DC 28 V
1 A, DC 110 V
Typical life 10,000 operations at 1 x I
N
20,000 operations mechanical
Ambient temperature -40...+60 °C (-40...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664A) withstand voltage degree
6 kV 3
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,300 V
pole/pole AC 3,300 V
main circuit/aux.circuit AC 2,200 V
aux. circuit 11-12/13-14 AC 1,000 V
Insulation resistance > 100 MΩ (DC 500 V)
Degree ef protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration
curves 02, 04, 05, B3, C3: 4 g (60-500 Hz), ± 0.30 mm (10-60 Hz)
curve 01: 3 g (60-500 Hz), ± 0.23 mm (10-60 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
curves 02, 04, 05, B3, C3: 50 g (11 ms) directions 1, 2, 3, 4, 5
30 g in direction 6
curve 01: 30 g (11 ms) in directions 1, 2, 3, 4, 5
20 g in direction 6
to IEC 60068-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-3, test Ca
Mass 410 (1-pole): approx. 290 g
520 (2-pole): approx. 580 g
530 (3-pole): approx. 870 g
Standard current ratings and typical internal resistance values
AC voltage
Number
of poles
Voltage
rating
Interrupting
capacity I
N
Power
factor
Interrupting
capacity I
N
Power factor
I
N 12...125 A
I
N 7 + 10 A
1 AC 240 V 5,000 A cosϕ = 0.7 3,500 A cosϕ = 0.8
2 AC 240 V 8,000 A cosϕ = 0.7 6,000 A cosϕ = 0.7
3 3 AC 415 V 5,000 A cosϕ = 0.7 3,000 A cosϕ = 0.85
DC voltage
Number
of poles
Voltage
rating
Interrupting
capacity I
N
Time
constant
Interrupting
capacity I
N
Time con-
stant
I
N 12...125 A
I
N 7 + 10 A
1 DC 110 V 3,000 A 13 ms 3,000 A L/R = 5 ms
1 DC 110 V 5,000 A 5 ms
2 DC 110 V 5,000 A 13 ms 3,000 A L/R = 5 ms
2 DC 110 V 10,000 A ≈ 0 ms
Curves 01, 02, 04, 05: Curves B3, C3:
Current
rating (A)
Internal resistance
(Ω) per pole
Current
rating (A)
Internal resistance
(Ω) per pole
10 0.033 7 0.033
16 0.015 10 0.015
20 0.010 12 0.015
25 0.0062 16 0.010
32 0.0039 20 0.0062
40 0.0031 25 0.0039
50 0.0022 32 0.0031
63 ≤ 0.002 40 0.0022
80 ≤ 0.002 50 ≤ 0.002
90 ≤ 0.002 63 ≤ 0.002
100 ≤ 0.002 80 ≤ 0.002
125 ≤ 0.002 100 ≤ 0.002
Authority Standard Rated voltage Current ratings
UL UL 1077
C22.2 No 235
AC 277 V 7...125 A (type 520)
High Performance Thermal-Magnetic Circuit Breakers 410/520/530-...
www.e-t-a.de
1646
2
1
Surface mounting
-1
rail mounting
(DIN EN 50 022-35x7,5)
-2
panel mounting
-4
Ordering information
Type No.
410 single pole (ratings > 125 A: suffix 17015 - parallel connection)
520 double pole
530 three pole
Terminal design - main terminals
K screw terminals
10-32 A pressure plate B5-DIN 46288 (curves B3/C3, 7-25 A)
40-63 A pressure plate B6-DIN 46288 (curves B3/C3, 32-63 A)
80-125 A terminal screw DIN 46206, sheet 2, form 1, M6 thread
Mounting
1 surface mounting
2 rail mounting (DIN EN 50022-35x7.5) or panel mounting
4 panel mounting with cylinder head screw M3.5
Magnetic trip curves
01 2.1-3 x I
N
AC (thyristor and rectifier protection)
02 7-10 x I
N
AC (motor and generator protection to EN 60947)
04 3.5-5 x I
N
AC (cable protection to EN 60947)
05 4-6 x I
N
AC (generator protection to EN 60947)
B3 3-5 x I
N
AC (cable protection to EN 60898)
C3 5-10 x I
N
AC (cable protection to EN 60898)
Auxiliary contacts optional (terminals M3.5)
Si one each N/O and N/C contact
Si1 one N/C (11,12)
Current ratings
7...125 A
520 - K - 1 - 01 - ... - 10 A ordering example
The exact number required can be built up from the table of choices shown above.
Ordering references for optional features should be omitted if not required.
Mounting methods
Dimensions
13
.512
15.4
.606
15.4
.606
114
4.49
120
4.72
120
4.72
7
.276
9
.354
9
.354
Max.
tightening
torque
≤ 32 A
≤ 63 A
≤ 125 A
Dimensions mm/in.
Terminal
B
pressure
plate B6
DIN 46288
terminal
screw
97
3.7 22 ø4.6
4.6
14.6
surface mounting
35
ø20
ø4
22
+0,5
44
+1
monting holes
26°
26°
106
90.5
71.5
41
6
92
16
symmetrical rail DIN EN 50022-35x7.5
G profile rail DIN EN 50035-G32 (not shown)
D
45
35
66
44
22
E
B
C
Si terminals M3.5
1 N/C
OFF
ON
type 410
type 520
M3.5 - thread max. 9 mm (.354 in.) deep
tightening torque max. 0.8 N
3
pole 1
pole 2
pole 3
1 N/O
Current
rating
type 530
Cross section (see DIN 46288)
with 1 or 2 equal
conductors
with 2 different
conductors
M5
M6
M6
CD
E
2.0 Nm
2.5 Nm
2.5 Nm
2.5 mm
2
to
10 mm
2
2.5 mm
2
to
10 mm
2
4 mm
2
to
16 mm
2
4 mm
2
and 6 mm
2
or
6 mm
2
to 16 mm
2
.236
3.56
1.64
4.17
.118
2.82
3.62 .630
1.77
1.38
.866
1.73
2.60
19
.748
.575
.181
3.82
.146 .181.866
.787
1.38
.157
.866
+.020
1.73
+.039
pressure
plate B5
DIN 46288
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
High Performance Thermal-Magnetic Circuit Breakers 410/520/530-...
www.e-t-a.de
1646 3
1
High Performance Thermal-Magnetic Circuit Breakers 410/520/530-...
line 1
line 1
line 1
6
I
>
3
I
>
I
>
3
5
I
>
line 1
2
2
11
12
13
14
4
I
>
2 4
I
>
11
12
13
14
I
>
2
11
12
13
14
Type 410-K Type 410-K-Si
Type 520-K-Si
Type 530-K-Si
… times rated current
Trip time in seconds
… times rated current
Trip time in seconds
12468
10 20 40
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
12468
10 20 40
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
01 0204
05
B3 C3
Typical time/current characteristics at +23 °C/+73.4 °F
Internal connection diagrams
Shock directions
1
2
4
3
5
6
Magnetic trip curves 01,02,04,05
AC/DC
1)
Magnetic trip curves B3,C3
AC/DC
1)
1)
Magnetic tripping currents are increased by 20% on DC
supplies.

530-K-1-02-SI-125A