https://www.phoenixcontact.com/us/products/3076604
09/08/2016Page1/10
High-current terminal block-UKH 70-3L/N/FE-F-3076604
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
High-current terminal block, Connection method:Screw connection, Number of positions:5, Cross section: 16
mm²-95 mm², AWG:4-3/0, Width:101.5 mm, Height:80 mm, Color:gray/blue/black-yellow, Mounting type:ct
screw connection
for direct mounting
Why buy this product
Reliable cable connection is ensured by three-point centering of the conductor in the prismatic sleeve base
Low contact resistance of the contact surface due to ribbing
Screw locking by means of spring-loaded elements in the clamping part
Key Commercial Data
Packing unit 1 STK
Minimum order quantity 2 STK
Custom tariff number 85369010
Country of origin China
Technical data
Environmental Product Compliance
China RoHS No hazardous substances above threshold values
General
Number of positions 5
Number of levels 1
Number of connections 10
Potentials 5
Nominal cross section 70 mm²
Color gray/blue/black-yellow
Insulating material PA
https://www.phoenixcontact.com/us/products/3076604
09/08/2016Page2/10
High-current terminal block-UKH 70-3L/N/FE-F-3076604
Technical data
General
Flammability rating according to UL 94 V0
Rated surge voltage 8 kV
Degree of pollution 3
Overvoltage category III
Insulating material group I
Maximum load current
192 A (in case of a 70 mm² conductor cross section, the maximum
load current must not be exceeded by the total current of all connected
conductors.)
Nominal current I
N
192 A
Nominal voltage U
N
1000 V
Open side panel No
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
Static insulating material application in cold -60 °C
Behavior in fire for rail vehicles (DIN 5510-2) Test passed
Flame test method (DIN EN 60695-11-10) V0
Oxygen index (DIN EN ISO 4589-2) >32 %
NF F16-101, NF F10-102 Class I 2
NF F16-101, NF F10-102 Class F 2
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Dimensions
Width 101.5 mm
Length 103.4 mm
Height 80 mm
Connection data
Connection method Screw connection
Connection in acc. with standard IEC 60947-7-1
Note
Note: Product releases, connection cross sections and notes on
connecting aluminum cables can be found in the download area.
Conductor cross section solid min. 16 mm²
https://www.phoenixcontact.com/us/products/3076604
09/08/2016Page3/10
High-current terminal block-UKH 70-3L/N/FE-F-3076604
Technical data
Connection data
Conductor cross section solid max. 95 mm²
Conductor cross section AWG min. 4
Conductor cross section AWG max. 3/0
Conductor cross section flexible min. 25 mm²
Conductor cross section flexible max. 70 mm²
Min. AWG conductor cross section, flexible 3
Max. AWG conductor cross section, flexible 2/0
Conductor cross section flexible, with ferrule without plastic sleeve min. 16 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 70 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 16 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 70 mm²
2 conductors with same cross section, solid min. 16 mm²
2 conductors with same cross section, solid max. 25 mm²
2 conductors with same cross section, stranded min. 16 mm²
2 conductors with same cross section, stranded max. 25 mm²
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, min.
16 mm²
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, max.
25 mm²
Stripping length 24 mm
Internal cylindrical gage A11
Screw thread M8
Tightening torque, min 8 Nm
Tightening torque max 10 Nm
Standards and Regulations
Connection in acc. with standard IEC 60947-7-1
Flammability rating according to UL 94 V0
Drawings

3076604

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Terminal Blocks UKH 70-3L/N/FE-F
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet