https://www.phoenixcontact.com/us/products/5603157
06/12/2014Page2/4
Relay Module-PLC-RSC-120UC/21 C1D2-5603157
Technical data
Coil side
Typical release time 15 ms
Operating voltage display Yellow LED
Protective circuit Bridge rectifier
Contact side
Contact type 1 PDT
Contact material AgSnO
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed for
voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in
adjacent modules. Potential bridging is then carried out with FBST 8-PLC...
or ...FBST 500...)
Minimum switching voltage 12 V AC/DC
Maximum inrush current on request
Min. switching current 10 mA
Limiting continuous current 6 A
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
1500 VA (for 250 V AC)
General
Test voltage relay winding/relay contact 4 kV AC (50 Hz, 1 min.)
Operating mode 100% operating factor
Mechanical service life
2 x 10
7
cycles
Inflammability class according to UL 94 V0
Pollution degree 3
Surge voltage category III
Mounting position any
Assembly instructions In rows with zero spacing
Connection data
Connection method Screw connection
Stripping length 8 mm
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG/kcmil max 14