3G3MV Inverters
Inverter PLC Specifications
Protective functions
Motor overload protection UL-recognized electronic thermal overload relay
Instantaneous overcurrent Motor coasts to a stop at approximately 250% inverter rated current
Overload Motor coasts to a stop after one minute at 150% rated output current
Overvoltage Motor coasts to a stop if DC bus voltage exceeds 410 V Motor coasts to a stop if DC bus voltage exceeds 820 V
Undervoltage Stops when DC bus voltage is approximately 200 V or
less (approx. 160 V or less for single-phase series)
Stops when DC bus voltage is approximately 400 V or
less
Momentary power loss Stops if power loss is 15 ms or more. By setting inverter, operation can be continued if power is restored within
approximately 0.5 s
Cooling method Cooling fan is provided for the following models:
200 V, 0.75 kW or larger inverters (3-phase)
200 V, 1.5 kW or larger inverters (single-phase)
Others models are self-cooling
Cooling fin overheat Protected by electronic circuit
Cooling fan fault Protected by electronic circuit (fan lock detection)
Stall prevention Individual levels during acceleration/running, enable/disable provided during coast to a stop
Ground fault Protected by electronic circuit (overcurrent level)
Power charge indication ON until the DC bus voltage becomes 50 V or less. RUN lamp stays ON or digital operator LED stays ON.
Environmental conditions
Enclosure rating Enclosed wall mounted NEMA 1
Location Indoor (free from corrosive gases and dust)
Ambient temperature Enclosed wall mounted NEMA 1: 14 to 105° F (-10 to +40°C), not frozen
Storage temperature -4 to 140°F (-20 to 60°C)
Humidity 95% RH or less (Non-condensing)
Elevation 1,000 m (3,281 feet) or below
Wiring distance 328 ft (100 m) or less between inverter and motor
Vibration
9.8 m/s
2
(1G) less than 20 Hz, up to 2 m/s
2
(0.2G) at 20 to 50 Hz
Other functions
Multi-function inputs Seven of the following input signals are selectable: Forward/reverse run (3-wire sequence), fault reset, external
fault (NO/NC contact input), multi-step speed operation, Jog command, accel/decel time select, external base
block (NO/NC contact input), speed search command, UP/DOWN command, accel/decel hold command,
LOCAL/REMOTE selection, communication/control circuit terminal selection, emergency stop fault, emergency
stop alarm, self test, PID control cancel, PID integral reset/hold
Multi-function outputs Following output signals are selectable (1 NO/NC contact output, 2 photo-coupler outputs): Fault, running, zero
speed, at frequency, frequency detection (output frequency = or = set value), during overtorque detection,
during undervoltage detection, minor error, during baseblock, operation mode, inverter run ready, during fault
retry, during UV, during speed search, data output through communication, PID feedback loss detection
Standard functions Voltage vector control, full-range automatic torque boost, slip compensation, DC injection braking current/time
at start/stop frequency reference bias/gain, MEMOBUS communications (RS-485/422, max. 19.2 K bps), PID
control, energy-saving control, parameter copy, frequency reference with built-in potentiometer
Model 3G3MV-P10CDT3-E 3G3MV-P10CDT-E
Type Full feature PLC installs on face of 3G3MV inverters with 1/4 to 10 HP rating
I/O points 6 input points (bi-directional input at 5 kHz; unidirectional input at 20 kHz)
4 output points (1 relay, 3 NPN transistor);
I/O can be set for interrupt inputs (50 μs response) or pulse outputs
Clock/calendar Yes N o
Encoder interface Yes Yes
Connectivity Direct HMI connection
Peripheral port
Serial ports: RS-232C, RS-422/485
Direct HMI connection
Peripheral port
RS-232C serial port
Memory backup Flash memory and battery Flash memory and capacitor
Dimensions 128 H x 68 W x 38.1 D mm
Software CX-Programmer included in CX-One