https://www.phoenixcontact.com/us/products/2912536
10/27/2014Page2/7
Relay Module-PLC-RSP- 60DC/21-21-2912536
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Coil side
Nominal input voltage U
N
60 V DC
Typical input current at U
N
10 mA
Typical response time 8 ms
Typical release time 10 ms
Operating voltage display Yellow LED
Protective circuit Protection against polarity reversal Polarity protection diode
Free-wheeling diode Damping diode
Contact side
Contact type 2 PDT
Contact material AgNi
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed for
voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in
adjacent modules. Potential bridging is then carried out with FBST 8-PLC...
or ...FBST 500...)
Minimum switching voltage 5 V AC/DC (at 10 mA)
Maximum inrush current 15 A (300 ms)
Min. switching current 10 mA (At 5 V)
Limiting continuous current 6 A
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
85 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
60 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity in acc. with DIN VDE 0660/IEC 60947 2 A (at 24 V, DC13)
0.2 A (at 250 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 250 V, AC15)
General
Operating mode 100% operating factor
Degree of protection RT III (Relay)
Mechanical service life
3 x 10
7
cycles
Inflammability class according to UL 94 V0