2701625

https://www.phoenixcontact.com/us/products/2701625
2/17/14Page1/5
Safety module-IB IL 24 LPSDO 8 V3-PAC-2701625
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four safe
digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy
Product description
The safety module is an output module from the Inline product range, designed for use in a SafetyBridge technology system. The safety module
can be used as part of an Inline station at any point within an INTERBUS, DeviceNet™, CANopen
®
, EtherNet/IP™, Sercos, Modbus, PROFINET or
PROFIBUS system. The transmission speed of the safety module can be set to 500 kbaud or 2 Mbaud using a switch. One transmission speed must
be used consistently within a station. The module has four safe digital outputs for two-channel assignment or eight safe digital outputs for single-
channel assignment. Depending on the installation and parameterization, in the SafetyBridge system the safety module can achieve the following safety
integrity:
- Up to SIL 3 according to standard EN 61508
- Up to SIL CL 3 according to standard EN 62061
- Up to Cat. 4/PL e according to standard EN ISO 13849-1
Product Features
Generation and monitoring of the SafetyBridge protocol
Processing of the parameterized safety logic
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 360.0 GRM
Custom tariff number 85389091
Country of origin Germany
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 48.8 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
https://www.phoenixcontact.com/us/products/2701625
2/17/14Page2/5
Safety module-IB IL 24 LPSDO 8 V3-PAC-2701625
Technical data
Ambient conditions
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Air pressure (operation) 80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection IP20
Interfaces
Fieldbus system INTERBUS
Name Inline local bus
Connection method Inline data jumper
Transmission speed 500 kBit/s / 2MBit/s
Digital outputs
Output name Digital outputs
Connection method Spring-cage connection
2, 3, 4-wire
Number of outputs 4 (with two-channel assignment)
8
Protective circuit Overload protection, short-circuit protection of outputs
Output voltage
24 V DC (U
S
- 1 V)
Nominal output voltage 24 V DC
Output current max. 6 A (Total current of all outputs, -25°C ... 50°C)
max. 4 A (Total current of all outputs, >50°C ... 55°C)
Maximum output current per channel 2 A
Maximum output current per group 3 A
Nominal load, inductive (see safety data)
Nominal load, lamp (see safety data)
Nominal load, ohmic (see safety data)
Power supply for module electronics
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC
Communications power U
L
7.5 V (via voltage jumper)
Current consumption max. 230 mA (from the local bus)
General
https://www.phoenixcontact.com/us/products/2701625
2/17/14Page3/5
Safety module-IB IL 24 LPSDO 8 V3-PAC-2701625
Technical data
General
Weight 200 g
Note on weight specifications with male connectors
Mounting type DIN rail
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Category according to EN 13849-1 4
Diagnostics messages
Short-circuit / overload of the digital outputs Error message in diagnostics
code (bus) and display by means of the LED on the motor
Inline potentials
Communications power U
L
7.5 V DC (see safety data)
Current consumption from U
L
max. 230 mA (see safety data)
Main circuit supply U
M
24 V DC (see safety data)
Supply voltage range U
M
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption from U
M
typ. 30 mA (all outputs set including actuator current)
max. 6.03 A
Segment supply voltage U
S
24 V (see safety data)
SafetyBridge properties
Connection to I/O modules max. 16 (safe digital I/O modules)
Logic memory 60 kByte
Classifications
eCl@ss
eCl@ss 4.0 27240409
eCl@ss 4.1 27240409
eCl@ss 5.0 27242205
eCl@ss 5.1 27242605
eCl@ss 6.0 27242605
eCl@ss 7.0 27242605
eCl@ss 8.0 27242605

2701625

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers Safety Logic Module 4 Out 2Ch, 8 Out 1Ch
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union