https://www.phoenixcontact.com/us/products/2701625
2/17/14Page2/5
Safety module-IB IL 24 LPSDO 8 V3-PAC-2701625
Technical data
Ambient conditions
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Air pressure (operation) 80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection IP20
Interfaces
Fieldbus system INTERBUS
Name Inline local bus
Connection method Inline data jumper
Transmission speed 500 kBit/s / 2MBit/s
Digital outputs
Output name Digital outputs
Connection method Spring-cage connection
2, 3, 4-wire
Number of outputs 4 (with two-channel assignment)
8
Protective circuit Overload protection, short-circuit protection of outputs
Output voltage
24 V DC (U
S
- 1 V)
Nominal output voltage 24 V DC
Output current max. 6 A (Total current of all outputs, -25°C ... 50°C)
max. 4 A (Total current of all outputs, >50°C ... 55°C)
Maximum output current per channel 2 A
Maximum output current per group 3 A
Nominal load, inductive (see safety data)
Nominal load, lamp (see safety data)
Nominal load, ohmic (see safety data)
Power supply for module electronics
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC
Communications power U
L
7.5 V (via voltage jumper)
Current consumption max. 230 mA (from the local bus)
General