4.Select Overload Protection (OLP) Mode
(1)Continuous Constant Current mode
(2)Delay Shutdown mode
Have the DIP switch position-1 set as ,and RST-10000 will work in continuous constant current mode when the output is overloaded and
Have the DIP switch position-1 set as ,and RST-10000 will shut down after 5 seconds of constant current operation, when the output is
the output voltage is greater than 50% of the rated output voltage.
overloaded or short-circuited.
5.Remote ON-OFF Control
※ The power supply can be turned ON-OFF by using the "Remote ON-OFF" function.
Switch open (Open) power supply OFF
Between ( ) and 12V-AUX( )Remote ON-OFF CN992 or CN993 pin10 CN991 pin1
Switch close (Short)
Output Status
power supply ON
Table 5.1
Fig 5.1
PIN1 12V-AUX
PIN3 GND-AUX
PIN10 RC+
PIN8 RC-
6.Alarm Signal Output
※ There are 4 alarm signals on CN991, and each signal can select two types of output circuit.
(1)Relay contact output {OTP1, OTP1-GND) ; (DC-OK1, DC-OK1-GND) ; (AC-FAIL1-GND,AC-FAIL1) ; (FAN-FAIL1-GND, FAN-FAIL1)}
(2)Open collector output {DC-OK2-GND, DC-OK2) ; (AC-FAIL2-GND, AC-FAIL2) ; (OTP2, OTP2-GND) ; (FAN-FAIL2, FAN-FAIL2-GND)}
Normally open contact. "Short" when the alarm arises. Relay contact rating(maximum) is 30V/1Aresistive.
An external voltage source is required for this function that is shown in Fig 6.2. These signals are isolated from output. The maximum sink current is
10mA and the maximum external voltage is 20V (there is a built-in 24V zener diode in inner circuitry).
Fig 6.1
Fig 6.2
R
V
DC-OK2
GND-AUX
12V-AUX
RST-10000
DC-OK2-GND
AC-FAIL2
OTP2
FAN-FAIL2
AC-FAIL2-GND
OTP2-GND
FAN-FAIL2-GND
10KΩ x4pcs
Application
Circuit
DIP
SW
CN993
CN992
CN991
+V
-V
CN993
CN991
SVR
RC+
GND-AUX
12V-AUX
RC-
RST-10000
SW