MAX1940
Triple USB Switch with Autoreset and
Fault Blanking
_______________________________________________________________________________________ 7
Pin Description
PIN NAME FUNCTION
1 ONA Control Input for Switch A. The active polarity of ONA is set by SEL (see Table 1).
2 IN1
Power Input. Connect all IN_ inputs together and bypass with a 0.1µF ceramic capacitor to GND. Load
conditions might require additional bulk capacitance to prevent pulling IN_ down.
3 IN2
Power Input. Connect all IN_ inputs together and bypass with a 0.1µF ceramic capacitor to GND. Load
conditions might require additional bulk capacitance to prevent pulling IN_ down.
4 IN3
Power Input. Connect all IN_ inputs together and bypass with a 0.1µF ceramic capacitor to GND. Load
conditions might require additional bulk capacitance to prevent pulling IN_ down.
5 ONB Control Input for Switch B. The active polarity of ONB is set by SEL (see Table 1).
6 IN4
Power Input. Connect all IN_ inputs together and bypass with a 0.1µF ceramic capacitor to GND. Load
conditions might require additional bulk capacitance to prevent pulling IN_ down.
7 IN5
Power Input. Connect all IN_ inputs together and bypass with a 0.1µF ceramic capacitor to GND. Load
conditions might require additional bulk capacitance to prevent pulling IN_ down.
8 ONC Control Input for Switch C. The active polarity of ONC is set by SEL (see Table 1).
9 FAULTC
Fault Indicator Output for Switch C. Open-drain output asserts low when switch C enters thermal shutdown,
undervoltage lockout, or a sustained (>20ms) current-limit or short-circuit condition.
10 OUTC
Power Output for Switch C. Bypass OUTC to GND with a 1µF ceramic capacitor. Load conditions might
require additional bulk capacitance. When disabled, OUTC goes into a high-impedance state.
11 SEL
Logic Input Polarity Select. SEL sets the active polarity of the ON_ inputs. Connect SEL high to set active-
high inputs. Connect SEL to GND to set active-low inputs.
12 FAULTB
Fault Indicator Output for Switch B. Open-drain output asserts low when switch B enters thermal shutdown,
undervoltage lockout, or enters a sustained (>20ms) current-limit or short-circuit condition.
13 OUTB
Power Output for Switch B. Bypass OUTB to GND with a 1µF ceramic capacitor. Load conditions might
require additional bulk capacitance. When disabled, OUTB goes into a high-impedance state.
14 GND Ground
15 OUTA
Power Output for Switch A. Bypass OUTA to GND with a 1µF ceramic capacitor. Load conditions might
require additional bulk capacitance. When disabled, OUTA goes into a high-impedance state.
16 FAULTA
Fault Indicator Output for Switch A. Open-drain output asserts low when switch A enters thermal shutdown,
undervoltage lockout, or a sustained (>20ms) current-limit or short-circuit condition.
MAX1940
Detailed Description
The MAX1940 triple current-limited USB power switch
provides three independent switches, each with its own
enable-control input and fault indicator (see Figure 1).
A logic input sets the active polarity of the enable con-
trol inputs. The fault indicators notify the system when
the current-limit, short-circuit, undervoltage lockout, or
thermal-shutdown threshold is exceeded.
The MAX1940 operates from a 4V to 5.5V input supply
and supplies a minimum output current of 700mA per
channel. A built-in current limit of 0.9A (typ) limits the
output current in the event of an overload condition.
Built-in short-circuit detection pulses the output current if
the output voltage falls below 1V, resulting in lower RMS
output current and reduced power dissipation in the
device. Independent thermal shutdown allows normal
operation to continue if one channel experiences a pro-
longed overload or short-circuit condition.
Low-R
ON
NMOS switches enable the MAX1940 to pro-
vide three switches in the space-saving 16-pin QSOP
package. An internal micropower charge pump gener-
ates the high-side supply needed for driving the gates
of these high-side switches. Separate current-limiting
and thermal-shutdown circuitry permits each switch to
operate independently, improving system robustness.
Triple USB Switch with Autoreset and
Fault Blanking
8 _______________________________________________________________________________________
FAULT LOGIC
20ms TIMERS
THERMAL
SHUTDOWN
CHARGE
PUMP
SWITCH B
(SEE SWITCH A)
SWITCH C
(SEE SWITCH A)
BIAS
REF
UVLO
OSC
25kHz
25mA
ILIM
SWITCH A
(EXPANDED)
IN2
IN_
FAULTA
FAULTB
FAULTC
OUTC
OUTA
IN2 IN3 IN4 IN5GND
ONC
ONB
SEL
IN1
ONA
OUTB
MAX1940
Figure 1. Functional Diagram
On/Off Control and
Undervoltage Lockout
SEL sets the active polarity of the logic inputs of the
MAX1940. Connect ON_ to the same voltage as SEL to
enable the respective OUT_ switch. Connect ON_ to
the opposite voltage as SEL to disable the respective
output (see Table 1). The output of a disabled switch
enters a high-impedance state.
The MAX1940 includes a UVLO circuit to prevent erro-
neous switch operation when the input voltage goes low
during startup and brownout conditions. Input voltages of
less than 3.4V inhibit operation of the device. FAULT_
asserts low during an undervoltage lockout condition.
Output Fault Protection and
Autoreset
The MAX1940 senses the switch output voltage and
selects continuous current limiting for V
OUT_
greater
than 1V, or short-circuit current limiting for V
OUT_
less
than 1V. When V
OUT_
is greater than 1V, the device
operates in a continuous current-limit mode that limits
output current to 0.9A. When V
OUT_
is less than 1V, the
device operates in short-circuit current-limit mode,
sourcing 1.2A pulses to the load. When either fault con-
dition persists for 20ms, the output turns off and its fault
flag is asserted. The output automatically restarts 20ms
after the short or overload is removed.
The MAX1940 detects short-circuit removal by sourcing
25mA from the output and monitoring the output volt-
age. When the voltage at the output exceeds 0.5V for
20ms, the fault flag resets, the output turns back on,
and the 25mA current source turns off. Active loads are
not expected to have measurable current when sup-
plied with less than 0.5V.
Thermal Shutdown
Independent thermal shutdown for each channel per-
mits normal operation of two switches to continue while
a third experiences a thermal fault. The switch turns off
and the FAULT_ output asserts low immediately when
the junction temperature exceeds +160°C. Thermal
shutdown does not utilize the 20ms fault-blanking time-
out period. The switch turns on again and FAULT_
returns high when the junction temperature cools by
+15°C. The switch cycles on and off if the overload
condition persists, resulting in a pulsed output that
reduces system power.
Fault Indicators
The MAX1940 provides an independent open-drain fault
output (FAULT_) for each switch. Connect FAULT_ to IN_
through a 100k pullup resistor for most applications.
FAULT_ asserts low when any of the following conditions
occur:
The input voltage is below the UVLO threshold.
The switch junction temperature exceeds the +160°C
thermal-shutdown temperature limit.
The switch is in current-limit or short-circuit current-
limit mode after the fault-blanking period (20ms)
expires.
The FAULT_ output deasserts after a 20ms delay once
the fault condition is removed. Ensure that the MAX1940
input bypass capacitance prevents glitches from trigger-
ing the FAULT_ outputs. Limit the input voltage slew rate
to 0.2V/µs to prevent erroneous FAULT_ indications.
To differentiate large capacitive loads from short cir-
cuits or sustained overloads, the MAX1940 has an
independent fault-blanking circuit for each switch.
When a load transient causes the device to enter cur-
rent limit, an internal counter monitors the duration of
the fault. For load faults exceeding the 20ms fault-
blanking time, the switch turns off, FAULT_ asserts low,
and the device enters autoreset mode (see the
Output
Fault Protection and Autoreset Mode
section). Only cur-
rent-limit and short-circuit faults are blanked. Thermal
overload faults and input voltage drops below the
UVLO threshold immediately turn the switch off and
assert FAULT_ low.
Fault blanking allows the MAX1940 to handle USB
loads that might not be fully compliant with USB specifi-
cations. The MAX1940 successfully powers USB loads
with additional bypass capacitance and/or large start-
up currents while protecting the upstream power
source. No fault is reported if the switch brings up the
load within the 20ms blanking period. See Table 2 for a
summary of current-limit and fault behavior.
MAX1940
Triple USB Switch with Autoreset and
Fault Blanking
_______________________________________________________________________________________ 9
SEL ON_ OUT_ BEHAVIOR
GND ON
GND
V
IN
OFF
GND OFF
V
IN
V
IN
ON
Table 1. On/Off Control

MAX1940EEE+

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Power Switch ICs - Power Distribution Triple USB Switch w/Autoreset
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet