MINI-PS- 12- 24DC/ 5-15DC/2
104346_en_01 PHOENIX CONTACT 4
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> +60°C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (At +25°C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ...150 Hz, 2.3 g
Shock 30g in all directions in acc. with IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)
Approvals
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing > Level 3
Contact discharge 8 kV (Contact discharge)
Discharge in air 8 kV (Air discharge)
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 3
Frequency range 80 MHz ... 3 GHz
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Signal 1 kV (Level 2 - asymmetrical cable to ground)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 2 kV (Level 3)
1 kV (Level 3)
Conducted interference EN 61000-4-6
Input/output Level 3
Frequency range 0.15 MHz ... 80 MHz (10 V)
Voltage dips EN 61000-4-11
Input (> 10 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Current approvals can be found for the product in the download area.