1
☎
USA (847) 827-7600 - www.e-t-a.com -
☎
CANADA (905) 764-9510Issue D
65
Voltage rating AC 240 V; DC 28 V
Current ratings 5...30 A
Typical life 1,000 operations at 2 x I
N
Ambient temperature -20...+60 °C (-4...+140 °F), <8A max. +40 °C
(104°F)
Insulation co-ordination Rated impulse Pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) Test voltage
operating area AC 3,000 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
200 A
Interrupting capacity I
N
U
N
(UL 1077/EN 60934 PC1) 5...16 A AC 240 V 2,000 A
18...30 A AC 120 V 2,000 A
5...30 A DC 28 V 2,000 A
Degree of protection operating area IP 40
(IEC 60529/DIN 40050) terminal area IP 00
Vibration 8 g (57-500 Hz) ±0.61 mm (10-57 Hz),
to IEC 60068-2-6, Test Fc,
10 frequency cycles/axis
Shock 30 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-3, test Ca
Mass approx. 16 g
Thermal Overcurrent Circuit Breaker 1658-...
Description
Very cost effective design to meet international requirements. No
exposed metal parts which are, or could become, current-carrying
except for terminals. R-type TO CBE to EN 60934.
● Manual reset, cycling trip free mechanism
● Extremely small and lightweight
● UL, CSA, VDE and EN 60934 (IEC 60934) approved
Technical data
1658-...
Typical applications
Battery chargers, consumer products, power supplies, motors.
Standard current ratings and typical voltage drop values
Current Voltage Current Voltage
rating (A) drop (mV) rating (A) drop (mV))
5 ≤ 150
6 ≤ 150
7 ≤ 150
8 ≤ 150
9 ≤ 150
10 ≤ 140
12 ≤ 140
15 ≤ 240
16 ≤ 240
20 ≤ 240
25 ≤ 240
30 ≤ 240
Approvals
Authority Voltage rating Current ratings
VDE (EN 60934) AC 240 V; DC 28 V 5...25 A
UL, CSA AC 250 V 5...15 A 1658-G...
AC 240 V 16 A 1658-G...
AC 120 V 30 A 1658-G...
AC 125 V 17...25 A 1658-G...
DC 28 V 5...30 A 1658-G...
Ordering information
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications without
notice is reserved.Product markings may not be exactly as the ordering codes. Errors and
omissions excepted.
1658-F
Type No.
1658 single pole thermal circuit breaker
Threadneck design
G21 manual reset type, 3/8"-27 threadneck
G41 manual reset type, 7/16"-28 threadneck
E00 manual reset without threadneck
F01 snap-in type
F02 press to reset, snap-in type
A21 auto reset type, 3/8"-27 threadneck
A41 auto reset type, 7/16"-28 threadneck
A00 auto reset type, without threadneck
A01 auto reset, snap-in type
Hardware
bulk mounted
configuration hex nut knurled nut hex nut knurled nut
00 0 0 0 0
01 1 (PAL) 0 0 0
02 1 (PAL) 1 0 0
03 0 0 1 (PAL) 0
04 0 0 1 (PAL) 1
05 0 1 1 (PAL) 0
06 0 1 0 0
07 1 0 0 0
08 2 0 0 0
09 1 1 0 0
10 0 0 0 1
12
(3/8-27 UNS) 1(PAL) 1 (plastic) 0 0
14
(3/8-27 UNS) 0 0 1 (PAL) 1 (plastic)
15
(3/8-27 UNS) 0 1 (plastic) 1 (PAL) 0
16
(3/8-27 UNS) 0 1 (plastic) 0 0
19
(3/8-27 UNS) 1 1 (plastic) 0 0
20
(3/8-27 UNS) 0 0 0 1 (plastic)
Terminals
P10 blade terminals A6.3-0.8
(QC .250)
P13 blade terminals A6.3-0.8 (QC .250), 90°
S80 straight screw terminals*
S83 90° bent screw terminals*
Current ratings
5 ... 30 A
1658 - G21 - 02 - P10 - 5 A Ordering example
* Screws and lock washers bulk shipped