http://www.tracopower.com Page 4 of 6
27 (1.06)
2.2 (0.09)
100.0
(3.94)
75.0 (2.95)
DC-ON LED
INPUT
1 2 3
OUTPUT
1 2
Case Dimensions
Industrial Power Supplies
TCL Series 24 to 240 Watt
TCL 024 and TCL-REM240 models
Weight: 140 g (4.9 oz)
Output Input
1 +Vout 1 AC Ground
2 –Vout 2 Neutral
3 Live
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
TCL–REM240 Redundancy Module
This module enables redundant operation of any two TCL models by decoupling
the 2 power supplies. It can also be used to separate sensitive loads from the main
power source.
Order Code Nominal Input
Voltage
Input Voltage
Range
Max Power
per Input
Output Voltage Output Current
max.
TCL–REM240
5...48 VDC 5...60 VDC 200 W Vin – 0.9 VDC
8 A
Specifications
Operating temperature –10°C to +70°C max. (14°F ... +158°F)
derating above +40°C (104°F): 1.5 %/K
Electromagnetic compatibility in correspondence to connected units
(no internal switching device)
Dimensions same as model TCL 024 (see page 4)
Connection detachable screw terminal block
Installation instructions www.tracopower.com/overview/tcl