UE10-3OS2D0 | UE10-3OS
SAFETY RELAYS
Test voltage
2kV (50Hz) (EN60439-1)
Input circuits: B1-B2/B3-B4
Input voltage
24VDC (15VDC... 30VDC)
Input current
≤ 500mA
Electrical output circuits: 13/14, 23/24, 33/34, 41/42, Y1/Y2
Response time
(≤ 20ms)
1)
Number of enable current (N/O) contacts
3, relevant for safety
Number of signalling current (N/C) contacts
1, not safety-relevant
Number of contactor monitoring (N/C) con-
tacts
1, external device monitoring (EDM)
Contact type
Positively driven
Contact material
Silver alloy, gold flashed
Switching voltage
Enable current contact 10VAC... 230VAC
10VDC... 300VDC
Signalling current contact 10VAC, 10VDC... 230VAC, 300VDC
Contactor monitoring contact 10VDC... 24VDC
Current-carrying capacity per OSSD
Enable current contact 5mA... 6A
Signalling current contact 5mA... 6A
Contactor monitoring contact 5mA... 100mA
Total current ≤ 12A
Usage category
AC-15/DC-13 (EN60947-5-1)
Rated operating current (voltage)
4A (230VAC) 360switching cycles/h
3A (230VAC) 3600switching cycles/h
4A (24VDC) 360switching cycles/h
2.5A (24VDC) 3600switching cycles/h
Mechanical life (relay contacts)
1x10
7
switching cycles
Electrical life (relay contacts)
2x10
6
switching cycles
1)
K1/K2.
Mechanical data
Dimensions (Wx Hx D)
22.5mmx 114mmx 96.5mm
Weight
0.2kg
Classifications
ECl@ss 5.0
27371990
ECl@ss 5.1.4
27371990
ECl@ss 6.0
27371819
ECl@ss 6.2
27371819
ECl@ss 7.0
27371819
ECl@ss 8.0
27371819
ECl@ss 8.1
27371819
ECl@ss 9.0
27371819
ETIM 5.0
EC001449
2018-03-29 13:18:26 | Online data sheet
Subject to change without notice
SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 3