SPECIFICATION
File Name:HLG-100H-SPEC 2018-05-29
100W Constant Voltage + Constant Current LED Driver
HLG-100H series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
MODEL
DC VOLTAGE
RATED CURRENT
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
CURRENT ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
Note.6
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
Note.8
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVER CURRENT
OVER VOLTAGE
OVER TEMPERATURE
47 ~ 63Hz
1.2A / 115VAC 0.55A / 230VAC 0.5A / 277VAC
<0.75mA / 277VAC
95 ~ 106%
Compliance to EN55015, EN55032 Class B, EN61000-3-2 Class C ( ) ; EN61000-3-3≧60% ,GB17743 and GB17625.1, EAC TP TC 020@ load
20 ~ 95% RH non-condensing
-40 ~ +80 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 60 )
10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes
192.2K hrs min. MIL-HDBK-217F (25 )℃
220*68*38.8mm (L*W*H)
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE
Note.3
ENVIRONMENT
SAFETY &
EMC
PROTECTION
Shut down o/p voltage, recovers automatically after temperature goes down
SHORT CIRCUIT
23 ~ 27V
28 ~ 34V
34 ~ 38V
41 ~ 46V
54 ~ 63V
47 ~ 53V 59 ~ 65V
93%
93%
93%
93%
93%93% 93%
±1.0% ±1.0% ±1.0%
±1.0%
±1.0%
±0.5% ±0.5% ±0.5%
±0.5%
±0.5%
±0.5% ±0.5% ±0.5%
±0.5%
±0.5%
±1.0%
±0.5%
±0.5%
±1.0%
±0.5%
±0.5%
20V
HLG-100H-20 HLG-100H-30 HLG-100H-42 HLG-100H-54HLG-100H-24 HLG-100H-36 HLG-100H-48
24V
36V
48V
150mVp-p
17 ~ 22V
150mVp-p
22 ~ 27V
200mVp-p
27 ~ 33V
200mVp-p
33 ~ 40V
200mVp-p
43 ~ 53V
54V
200mVp-p
49 ~ 58V
42V
200mVp-p
38 ~ 46V
Constant current limiting, recovers automatically after fault condition is removed
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61547, EN55024, industry level ( )
light
surge immunity Line-Earth 4KV, Line-Line 2KV , EAC TP TC 020
Constant current limiting, recovers automatically after fault condition is removed
Shut down o/p voltage with auto-recovery or re-power on to recovery
3 ~ 4.8A 2.5 ~ 4A 2 ~ 3.2A
1.65 ~ 2.65A
1.25 ~ 2A 1.1 ~ 1.77A
1.4 ~ 2.28A
4.8A 4A
3.2A
2.65A
2A
96W 96W 96W
95.4W
96W
1.77A
95.58W
2.28A
95.76W
1.12Kg; 12pcs/14.4Kg/0.8CUFT
EMC IMMUNITY
EMC EMISSION
Note.8
UL8750 , CSA C22.2 No. 250.0-08; 61347-1, 61347-2-13 independent;
(type”HL”) EN/AS/NZS EN/AS/NZS GB19510.1,GB19510.14,
IP65 or IP67, J61347-1, J61347-2-13 approved ; design refer to UL60950-1, TUV EN60950-1, EAC TP TC 004
COLD START 60A(t =415 s measured at 50% I ) at 230VACwidth peak ; Per NEMA 410
μ
TOTAL HARMONIC DISTORTION
CONSTANT CURRENT REGION
Note.4
10 ~ 20V 12 ~ 24V 15 ~ 30V
18 ~ 36V
24 ~ 48V 27 ~ 54V
21 ~ 42V
MAX. No. of PSUs on 16A
CIRCUIT BREAKER
4 units (circuit breaker of type B) / 8 units (circuit breaker of type C) at 230VAC
30V
1. All parameters NOT specially mentioned are measured at 230VAC input, rated current and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Please refer to "DRIVING METHODS OF LED MODULE".
5. De rating may be needed under low input voltages. Please .- refer to STATIC CHARACTERISTIC sections for details
6. Length of set up time is measured at first cold start. Turning ON/OFF the driver may lead to increase of the set up time.
7. driver
The is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the
complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
8.To fulfill requirements of the latest ErP regulation for lighting fixtures, this LED can only be used behind a switch without permanently
driver
connected to the mains.
9. This series meets the typical life expectancy of >62,000 hours of operation when Tcase, particularly tc point (or TMP, per DLC), is about 80 or less.℃
10. Please refer to the warranty statement on MEAN WELL's website at http://www.meanwell.com
11. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Adjustable for A/AB-Type only (via built-in potentiometer)
Adjustable for A/AB-Type only (via built-in potentiometer)
16ms / 115VAC, 230VAC
1200ms,50ms/115VAC 500ms,50ms/230VAC
90 ~ 305VAC 127 ~ 431VDC
(Please refer to "STATIC CHARACTERISTIC" section)
PF 0.98/115VAC, PF 0.95/230VAC, PF 0.93/277VAC @ full load≧≧≧
(Please refer to " " section)POWER FACTOR (PF) CHARACTERISTIC
THD< 20% (@ load 60% / 115VAC,230VAC; @ load 75% / 277VAC)≧≧
(Please refer to TOTAL HARMONIC DISTORTION (THD) section)""
MAX. CASE TEMP.
Tcase= +80℃
Tcase= -40 ~ +80℃
(Please refer to "OUTPUT LOAD vs TEMPERATURE" section)