https://www.phoenixcontact.com/us/produkte/2703017
10.10.2012Page3/6
Transformer terminal block-TRK 10 GY-2703017
Technical data
Technical data
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Oscillation, broadband noise test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
Shock form Half-sine
Acceleration 5 g
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Shock test result Test passed
Temperature index, insulating material (DIN EN 60216-1 (VDE
0304-21))
125 °C
Connection data
Conductor cross section solid min. 2.5 mm²
Conductor cross section solid max. 10 mm²
Conductor cross section stranded min. 4 mm²
Conductor cross section stranded max. 10 mm²
Conductor cross section AWG/kcmil min. 14
Conductor cross section AWG/kcmil max 8
Conductor cross section stranded, with ferrule without plastic
sleeve min.
2.5 mm²
Conductor cross section stranded, with ferrule without plastic
sleeve max.
6 mm²
Conductor cross section stranded, with ferrule with plastic sleeve
min.
2.5 mm²
Conductor cross section stranded, with ferrule with plastic sleeve
max.
6 mm²
2 conductors with same cross section, solid min. 2.5 mm²
2 conductors with same cross section, solid max. 10 mm²
2 conductors with same cross section, stranded min. 4 mm²
2 conductors with same cross section, stranded max. 10 mm²
2 conductors with same cross section, stranded, ferrules without
plastic sleeve, min.
2.5 mm²
2 conductors with same cross section, stranded, ferrules without
plastic sleeve, max.
6 mm²
2 conductors with same cross section, stranded, TWIN ferrules
with plastic sleeve, min.
1.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules
with plastic sleeve, max.
4 mm²
Connection method Screw connection
Stripping length 16 mm
Internal cylindrical gage A4
Screw thread M5
Tightening torque, min 4 Nm