FLT-CP-PLUS-2S-350 Order No.: 2882666
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882666
PHOENIX CONTACT Inc., USA Page 3 / 7
http://www.phoenixcon.com Jul 26, 2011
Lightning test current (10/350) µs, specific energy 160.00 kJ/Ω (L-N)
Lightning test current (10/350) µs, peak value l
imp
25 kA (per channel L-N)
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE) ≤ 1.5 kV
Protection level U
P
(L-N) ≤ 1.5 kV
Protection level U
P
(L-PE) ≤ 2.5 kV
Protection level UP (N-PE) ≤ 1.5 kV
Response time (L-N) ≤ 100 ns
Response time (L-PE) ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Max. required backup fuse with branch wiring 315 A (gL/gG)
Max. required backup fuse with V-type through
wiring
125 A (gL/gG)
Recommended backup fuse maximum 160 A (gL/gG, 125 A with serial through wiring)
Short-circuit resistance I
P
with max. backup fuse
(effective)
50 kA
Short-circuit current self-quenching 100 A (effective (N-PE))
Follow current quenching capacity If (L-N) 50 kA (264 V AC)
25 kA (350 V AC)
Follow current quenching capacity If (N-PE) 100 A
Connection, protective circuit
Connection method Screw terminal blocks
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 18 mm
Conductor cross section stranded min. 2.5 mm²
Conductor cross section stranded max. 25 mm²
Conductor cross section solid min. 2.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section AWG/kcmil min. 13
Conductor cross section AWG/kcmil max 2
Remote indicator contact
Connection name Remote fault indicator contact