SF4D-DC5V

–1–
ASCTB120E 201408-T
ORDERING INFORMATION
TYPES
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
Flat type safety relays
(double contact)
SF RELAYS
Double contact type
Contact arrangement Nominal coil voltage Part No.
2 Form A 2 Form B
5V DC SF2D-DC5V
12V DC SF2D-DC12V
24V DC SF2D-DC24V
48V DC SF2D-DC48V
60V DC SF2D-DC60V
4 Form A 4 Form B
5V DC SF4D-DC5V
12V DC SF4D-DC12V
24V DC SF4D-DC24V
48V DC SF4D-DC48V
60V DC SF4D-DC60V
2 Form A 2 Form B
4 Form A 4 Form B
RoHS compliant
FEATURES
1. High contact reliability
High contact reliability is achieved
through the use of a double contact.
2. Forced operation contacts
N.O. and N.C. side contacts are
connected through a card so that one
interacts with the other in movement. In
case of a contact welding, the other
keeps a min. 0.5mm .020inch contact
gap.
3. Independent operation contacts
(4 Form A 4 Form B)
There are 4 points of forced operation
contacts.
Each pair of contacts is free from the
main armature and is independent from
each other. So if a N.O. pair of contacts
are welded, the other 3 N.O. contacts are
not effected (operate properly) That
enables to plan a circuit to detect welding
or go back to the beginning condition.
4. Separated chamber structure
N.O. and N.C. side contacts are put in
each own space surrounded with a card
and a body-separater. That prevents
short circuit between contacts, which is
caused by their springs welding or
damaged.
5. High breakdown voltage
High breakdown voltage 2,500 Vrms
between contacts and coil.
6. High sensitivity
Realizes thin shape and high sensitivity
(500 mW nominal operating power) by
utilizing high-efficiency polarized
magnetic circuit with 4-gap balanced
armature.
7. Complies with safety standards
Standard products are UL, CSA, TÜV
and SEV certified. Conform to European
standards. TÜV certified. Complies with
SUVA European standard.
TYPICAL APPLICATIONS
1. Industrial equipment such as
presses and machine tools
2. Elevators and other kinds of
hoisting mechanisms, conveyor
equipment.
Contact arrangement
2: 2 Form A 2 Form B
4: 4 Form A 4 Form B
SF D
Nominal coil voltage
DC 5, 12, 24, 48, 60V
Note: Certified by UL, CSA, TÜV and SEV
SF Double contact type
–2–
ASCTB120E 201408-T
RATING
1. Coil data
2. Specifications
Notes: *1. This value can change due to the switching frequency, environmental conditions and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. The upper limit of the ambient temperature is the maximum temperature that can satisfy the coil temperature rise value. Refer to Usage, transport and storage
conditions in NOTES.
Contact
arrangement
Nominal coil
voltage
Pick-up voltage
(at 20°C 68°F)
Drop-out voltage
(at 20°C 68°F)
Nominal coil current
[±10%]
(at 20°C 68°F)
Coil resistance
[±10%]
(at 20°C 68°F)
Nominal operating
power
(at 20°C 68°F)
Max. applied
voltage
(at 20°C 68°F)
2 Form A 2 Form B
5V DC
75%V or less of
nominal voltage
(Initial)
10%V or more of
nominal voltage
(Initial)
100mA 50Ω
500mW
120%V of
nominal voltage
12V DC 41.7mA 288Ω
24V DC 20.8mA 1,152Ω
48V DC 10.4mA 4,608Ω
60V DC 8.3mA 7,200Ω
4 Form A 4 Form B
5V DC
75%V or less of
nominal voltage
(Initial)
15%V or more of
nominal voltage
(Initial)
100mA 50Ω
500mW
12V DC 41.7mA 288Ω
24V DC 20.8mA 1,152
Ω
48V DC 10.4mA 4,608Ω
60V DC 8.3mA 7,200Ω
Characteristics Item Specifications
Contact
Arrangement 2 Form A 2 Form B 4 Form A 4 Form B
Contact resistance (Initial) Max. 30 mΩ (By voltage drop 6 V DC 1A)
Contact material Au-flashed AgSnO
2 type
Rating
Nominal switching capacity (resistive load) 6A 250V AC, 6A 30V DC
Max. switching power (resistive load) 1,500VA 180W
Max. switching voltage 440V AC, 30V DC
Max. switching current 6A
Nominal operating power 500mW
Min. switching capacity (Reference value)*
1
100mA 5V DC
Electrical
characteristics
Insulation resistance (Initial) Min. 1,000MΩ (at 500V DC) Measurement at same location as “Breakdown voltage” section.
Breakdown voltage
(Initial)
Between open contacts 1,300 Vrms for 1min. (Detection current: 10mA)
Between contact sets 2,500 Vrms for 1min. (Detection current: 10mA)
Between contact and coil 2,500 Vrms for 1min. (Detection current: 10mA)
Temperature rise (coil) (at 20° 68°F)
Max. 45°C 113°F
(By resistive method, nominal voltage applied to the coil; contact carrying current: 6A)
Operate time Max. 30ms (Nominal voltage applied to the coil, excluding contact bounce time.)
Release time
Max. 15ms (Nominal voltage applied to the coil, excluding contact bounce time.)
(without diode)
Mechanical
characteristics
Shock resistance
Functional Min. 294 m/s
2
(Half-wave pulse of sine wave: 11 ms; detection time: 10μs)
Destructive Min. 980 m/s
2
(Half-wave pulse of sine wave: 6 ms)
Vibration resistance
Functional 10 to 55 Hz at double amplitude of 2 mm (Detection time: 10μs)
Destructive 10 to 55 Hz at double amplitude of 2 mm
Expected life
Mechanical Min. 10
7
(at 180 times/min.)
Electrical Min. 10
5
(at 20 times/min.)
Conditions
Conditions for operation, transport and storage*
2
Ambient temperature: –40°C to +70°C –40°F to +158°F
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
Max. Operating speed 180 times/min.
Unit weight Approx. 38g 1.34oz Approx. 47g 1.66oz
SF Double contact type
–3–
ASCTB120E 201408-T
REFERENCE DATA
DIMENSIONS (mm inch)
1. 2 Form A 2 Form B
2. 4 Form A 4 Form B
1. Operate/release time (without diode)
Tested sample: SF2D-DC24V (2 Form A 2 Form B)
Quantity: n = 20
2. Temperature rise
Tested sample: SF4D-DC24V (4 Form A 4 Form B)
Quantity: n = 6
Coil applied voltage: 100%V, 120%V
Contact carry current: 6A
3. Ambient temperature characteristics
Tested sample: SF4D-DC24V (4 Form A 4 Form B)
Quantity: n = 6
10
20
30
0
40
50
8070 10090 120 130110
Coil applied voltage, %V
Operate/release time, ms
Operate time
Release time
Min.
Max.
x
Min.
Max.
x
5
10
15
0
20
25
30
120100 110
Coil applied voltage, %V
Inside the coil
Contact
Temperature rise, °C
-40 -20 0
20
40 60 80
-50
100
50
-100
Drop-out voltage
Pick-up voltage
Ambient
temperature, °C
Rate of
change, %
The CAD data of the products with a CAD Data mark can be downloaded from: http://industrial.panasonic.com/ac/e/
External dimensions
General tolerance: ±0.3 ±.012
12.7
53.3±0.5
12.712.7
5.08
6587
109
1
2
1211
16±0.5
12.7
3.0±0.5
0.5
0.48
25.0
7.62
1.0
0.30
.500
2.098±.020
.500.500
.200
.630±.020
.500
.118±.020
.020
.019
.984
.300
.039
1.0
.039
.012
Schematic (Bottom view)
PC board pattern (Bottom view)
Tolerance: ±0.1 ±.004
5
1
2
678
9 101112
2.54
2.54
10-1.4 dia. holes
.100
.100
10-.055 dia. holes
CAD Data
External dimensions
General tolerance: ±0.3 ±.012
12.7
53.3±0.5
12.712.7
5.08
65
1817 2019
87
109
1413 1615
1
2
1211
16±0.5
12.7
7.62
7.62
3.0±0.5
0.5
33±0.5
7.62
1.0
0.48
0.48
0.30
.500
2.098±.020
.500.500
.200
.630±.020
.500
.300
.300
.118±.020
.020
1.299±.020
.300
.039
1.0
.039
.019
.019
.012
Schematic (Bottom view)
PC board pattern (Bottom view)
Tolerance: ±0.1 ±.004
1
13
5
2
14
6
15
7
16
8
9
17
10
18
11
19
12
20
2.54
2.54
18-1.4 dia. holes
.100
.100
18-.055 dia. holes
CAD Data

SF4D-DC5V

Mfr. #:
Manufacturer:
Panasonic Industrial Devices
Description:
General Purpose Relays Polarized PowerRelay 4 Form A 4 Form B
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: