BK/MDA-6-R

Description
Time-delay
Optional axial leads available
1/4” x 1-1/4” (6.35 x 31.75mm) physical size
Ceramic tube, nickel-plated brass endcap construction
UL Listed product meets standard 248-14
Agency Information
UL Listed Card: MDA
2
/
10 - 20A (Guide JDYX, File E19180)
UL Recognized Card: MDA 25 - 30A (Guide JDYX2, File E19180)
CSA Certification Card: MDA
2
/
10 - 20 (Class No. 1422-01)
CSA Component Acceptance: MDA 25-30A (Class No. 1422-30)
0711 BU-SB11875 Page 1 of 2 Data Sheet 2002
Specifications
AC Interrupting
Part Voltage Rating Rating* (amps) DC Interrupting Typical DC Cold Typical Typical Voltage
Number Vac Vdc 250V 125V Rating (amps) 125V Resistance** (Ω) Melting I
2
t† AC Drop‡
MDA-1/4-R 250 - 35 10000 - 8.7 0.748 4.00
MDA-1/2-R 250 - 35 10000 - 1.78 2.53 1.42
MDA-3/4-R 250 - 35 10000 - 0.82 8.58 1.31
MDA-1-R 250 - 35 10000 - 0.56 12.21 1.03
MDA-1-1/2-R 250 - 100 10000 - 0.2565 27.5 0.691
MDA-2-R 250 - 100 10000 - 0.17 70.4 0.623
MDA-2-1/2-R 250 - 200 10000 - 0.068 31.79 0.213
MDA-3-R 250 - 200 10000 - 0.0525 44.99 0.182
MDA-4-R 250 - 200 10000 - 0.03575 147.4 0.162
MDA-5-R 250 - 200 10000 - 0.0256 380.49 0.145
MDA-6-R 250 - 200 10000 - 0.02035 587.73 0.141
MDA-7-R 250 - 200 10000 - 0.0165 638.33 0.137
MDA-8-R 250 - 200 10000 - 0.013 1038.4 0.134
MDA-10-R 250 - 200 10000 - 0.00925 1620.43 0.135
MDA-12-R 250 - 750 10000 - 0.00755 125.18 0.128
MDA-15-R 250 - 750 10000 - 0.00565 336.82 0.107
MDA-20-R 250 125 1500 10000 10000 0.004065 483.45 0.095
MDA-25A-R 250 125 1500 10000 10000 0.0031 734.69 0.105
MDA-30A-R 250 125 1500 10000 10000 0.002465 1096.7 0.110
* Interrupting Ratings (Measured at 70% - 80% power factor on AC. The interrupting ratings for 25A, 30A were measured at 90% - 100% power factor on AC)
** DC Cold Resistance (Measured at _<10% of rated current)
Typical Melting I
2
t (A
2
Sec) (I
2
t was measured at listed interrupting rating and rated voltage)
Typical Voltage Drop (Voltage drop was measured at 25°C ambient temperature at rated current)
Electrical Characteristics
Rated Current Amp Rating Opening Time
100% None
1/4 - 30A 135% 60 Minutes Max.
200% 120 Seconds Max.
Ordering
Specify packaging, product and option code.
38.10
(1.500)
32.82
(1.292)
38.10
(1.500)
6.76
(0.266)
31.75
(1.250)
6.35
(0.250)
DIA. OF LEADS
0–15 AMP:
20–30 AMP:
0.81
(0.032)
1.02
(0.040)
Environmental Data
Shock: 1/100A and 8/10A – MIL-STD-202, Method 213,
Test Condition I; 1A thru 30A – MIL-STD-202, Method 213,
Test Condition J
Vibration: 1/100A and 8/10A – MIL-STD-202, Method 201;
1/4A thru 30A – MIL-STD-202, Method 204, Test Condition C
(Except 5g, 500Hz)
Dimensions - mm (in)
Drawing Not to Scale
1/4” x 1 1/4” Time-Delay Ceramic Tube Fuses
MDA Series
Option Code
Option Code Description
B Sealed to withstand aqueous cleaning (Board Washable)
V Axial leads - copper tinned wire with nickel plated brass overcaps
Packaging Code
Packaging Code Prefix Description
BK- 100 fuses packed into a cardboard carton
BK1- 1,000 fuses packed into a cardboard carton
BK8- 8,000 fuses packed into a cardboard carton
0711 BU-SB11875 Page 2 of 2 Data Sheet 2002
TIME IN SECONDS
TIME IN SECONDS
CURRENT IN AMPS
CURRENT IN AMPS
1/4
1/2
1
2
3-2/10
4
5
6-1/4
10
12
15
20
25
30
Time-Current Curves
© 2011 Cooper Bussmann
www.cooperbussmann.com
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con-
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Life Support Policy: Cooper Bussmann does not authorize the use of any of its products for use in life support devices or systems without the express written approval of an officer of the Company. Life sup-
port systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result
in significant injury to the user.

BK/MDA-6-R

Mfr. #:
Manufacturer:
Description:
Cartridge Fuses SMALL DIM. FUSE
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: