Thermal-Magnetic Circuit Breaker 2210-S2...
www.e-t-a.de
1646
1
1
Description
Typical applications
Technical data
One, two and three pole thermal-magnetic circuit breakers with trip free
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC
934). Designed for panel or plug-in mounting. Available with auxiliary
contacts (1 x N/O, 1 x N/C) for status signalling. Two and three pole
models are internally linked to ensure that both/all poles trip in the
event of an overload on one pole, even if the actuator is held in the ON
position. A choice of characteristic curves further extends the range
of applications possibilities for these CBEs. Special auxiliary contact
versions for industrial atmosphere and low voltages (e. g. 5 V) available
on request.
Approved to CBE standard EN 60934 (IEC 60934).
Suitable for use in distribution rails – see section Power Distribution
Systems.
Process control equipment, robotics, machine tool control, communications
systems, instrumentation, rail vehicles. Special versions, e.g. for aggressive
environmental conditions and low voltages (e. g. 5 V) on request.
2210-S2..
For further details please see chapter: Technical Information
Voltage rating AC 250 V*; 3 AC 433 V (50-60Hz); DC 65 V
(*UL: AC 277/480 V; DC 65 V)
Current rating range 0.1...25 A for curves M1, T1
0.1...16 A for curves F1, F2, M3
Auxiliary circuit 1 A, AC 240 V/DC 65 V, resistive
Typical life 10,000 operations at 1 x I
N
, inductive
Ambient temperature -30...+60 °C (-22...+140 °F) T 60
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 1,500 V
aux. circuit 11-12/23-24 AC 1,000 V
pole/pole AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.1...5 A 400 A
6...25 A 800 A
curves F1, F2, M1, T1: 0.1...16 A 2,500A (at DC 32 V)
curve M3: 0.1...2 A AC 200 A DC 400 A
Interrupting capacity (UL 1077)
Degree of protection operating area IP30
(IEC 60529/DIN 40050) terminal area IP00
Vibration curves F1, F2:
3 g (57-500 Hz), ± 0.23 mm (10-57 Hz)
curves M1, M3, T1:
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock curves F1, F2:
25 g (11 ms), directions 1, 2, 3, 4, 5
10 g (11 ms), direction 6
curves M1, M3, T1:
25 g (11 ms), directions 1, 2, 3, 4, 5
20 g (11 ms), direction 6
to IEC 60068-2-27, test Ea
Corrosion 96 hours in 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 50 g per pole
I
N
0.1...16 A 20...25 A
AC 277 V 1-pole 5,000 A 2,000 A
AC 277/480 V 2-/3-pole
5,000 A 2,000 A
DC 65 V 2,000 A 2,000 A
Standard current ratings and typical internal resistance values
Current
rating (A)
Internal resistance (Ω)
F1 F2 M1 T1 M3
fast acting
for DC only
fast acting
delay
for AC+DC
standard
for AC+DC
delayed
low
resistance
only for AC
standard
delay
0.1 162 162 92 81 42
0.2 39.3 39.3 26.1 24.2 11.7
0.3 17.5 17.5 11.6 10.4 5.6
0.4 9.2 9.2 6.6 6.0 2.9
0.5 6.8 6.8 4.1 3.9 1.75
0.6 4.2 4.2 3 2.7 1.42
0.8 2.8 2.8 1.65 1.53 0.75
1 1.6 1.6 1.10 0.98 0.5
1.5 0.78 0.78 0.47 0.42 0.22
2 0.42 0.42 0.28 0.24 0.136
2.5 0.26 0.26 0.183 0.17 0.083
3 0.18 0.18 0.124 0.12 0.057
4 0.12 0.12 0.077 0.073 0.041
5 0.092 0.092 0.063 0.055 0.032
6 0.054 0.054 0.045 0.039 0.021
8 0.025 0.025 ≤ 0.02 ≤ 0.02 ≤ 0.02
10 0.022 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
12 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
16 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
20 - - ≤ 0.02 ≤ 0.02 -
25 - - ≤ 0.02 ≤ 0.02 -
Preferred types Standard current ratings (A)
1-pole:
1 2 4 6 8 10 16
2210-S211-P1F1-H111-
x x x x x
2210-S211-P1M1-H111-
x x x x x x x
2210-S211-P1M1-Z111-
x x x x x x x
2-pole:
2210-S221-P1M1-H111-
x x x x x x x
2210-S221-P1M1-H211-
x x x x x x x
Preferred types