2210-S221-P1T1-Z241-8A

Thermal-Magnetic Circuit Breaker 2210-S2...
www.e-t-a.de
1646
1
1
Description
Typical applications
Technical data
One, two and three pole thermal-magnetic circuit breakers with trip free
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC
934). Designed for panel or plug-in mounting. Available with auxiliary
contacts (1 x N/O, 1 x N/C) for status signalling. Two and three pole
models are internally linked to ensure that both/all poles trip in the
event of an overload on one pole, even if the actuator is held in the ON
position. A choice of characteristic curves further extends the range
of applications possibilities for these CBEs. Special auxiliary contact
versions for industrial atmosphere and low voltages (e. g. 5 V) available
on request.
Approved to CBE standard EN 60934 (IEC 60934).
Suitable for use in distribution rails – see section Power Distribution
Systems.
Process control equipment, robotics, machine tool control, communications
systems, instrumentation, rail vehicles. Special versions, e.g. for aggressive
environmental conditions and low voltages (e. g. 5 V) on request.
2210-S2..
For further details please see chapter: Technical Information
Voltage rating AC 250 V*; 3 AC 433 V (50-60Hz); DC 65 V
(*UL: AC 277/480 V; DC 65 V)
Current rating range 0.1...25 A for curves M1, T1
0.1...16 A for curves F1, F2, M3
Auxiliary circuit 1 A, AC 240 V/DC 65 V, resistive
Typical life 10,000 operations at 1 x I
N
, inductive
Ambient temperature -30...+60 °C (-22...+140 °F) T 60
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 1,500 V
aux. circuit 11-12/23-24 AC 1,000 V
pole/pole AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.1...5 A 400 A
6...25 A 800 A
curves F1, F2, M1, T1: 0.1...16 A 2,500A (at DC 32 V)
curve M3: 0.1...2 A AC 200 A DC 400 A
Interrupting capacity (UL 1077)
Degree of protection operating area IP30
(IEC 60529/DIN 40050) terminal area IP00
Vibration curves F1, F2:
3 g (57-500 Hz), ± 0.23 mm (10-57 Hz)
curves M1, M3, T1:
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock curves F1, F2:
25 g (11 ms), directions 1, 2, 3, 4, 5
10 g (11 ms), direction 6
curves M1, M3, T1:
25 g (11 ms), directions 1, 2, 3, 4, 5
20 g (11 ms), direction 6
to IEC 60068-2-27, test Ea
Corrosion 96 hours in 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 50 g per pole
I
N
0.1...16 A 20...25 A
AC 277 V 1-pole 5,000 A 2,000 A
AC 277/480 V 2-/3-pole
5,000 A 2,000 A
DC 65 V 2,000 A 2,000 A
Standard current ratings and typical internal resistance values
Current
rating (A)
Internal resistance (Ω)
F1 F2 M1 T1 M3
fast acting
for DC only
fast acting
delay
for AC+DC
standard
for AC+DC
delayed
low
resistance
only for AC
standard
delay
0.1 162 162 92 81 42
0.2 39.3 39.3 26.1 24.2 11.7
0.3 17.5 17.5 11.6 10.4 5.6
0.4 9.2 9.2 6.6 6.0 2.9
0.5 6.8 6.8 4.1 3.9 1.75
0.6 4.2 4.2 3 2.7 1.42
0.8 2.8 2.8 1.65 1.53 0.75
1 1.6 1.6 1.10 0.98 0.5
1.5 0.78 0.78 0.47 0.42 0.22
2 0.42 0.42 0.28 0.24 0.136
2.5 0.26 0.26 0.183 0.17 0.083
3 0.18 0.18 0.124 0.12 0.057
4 0.12 0.12 0.077 0.073 0.041
5 0.092 0.092 0.063 0.055 0.032
6 0.054 0.054 0.045 0.039 0.021
8 0.025 0.025 ≤ 0.02 ≤ 0.02 ≤ 0.02
10 0.022 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
12 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
16 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
20 - - ≤ 0.02 ≤ 0.02 -
25 - - ≤ 0.02 ≤ 0.02 -
Preferred types Standard current ratings (A)
1-pole:
1 2 4 6 8 10 16
2210-S211-P1F1-H111-
x x x x x
2210-S211-P1M1-H111-
x x x x x x x
2210-S211-P1M1-Z111-
x x x x x x x
2-pole:
2210-S221-P1M1-H111-
x x x x x x x
2210-S221-P1M1-H211-
x x x x x x x
Preferred types
Thermal-Magnetic Circuit Breaker 2210-S2...
www.e-t-a.de
1646
2
1
Installation drawing
Dimensions
0
0
2 A
M1
0
11 1224
Z
25°
25°
OFF
ON
10.5
1
19
43
68
3.5
10
.268
6x6.8 = 40.8
polarizing tooth
30.5
18
37.5
25
12.5
11.5
12.512.5
blade terminals
DIN 46244-A6.3-0.8
(QC .250)
50
32
5.5
16
unit III
unit II
unit I
ø11
12
multipole devices
123
.472
.217
.433
.630
1.26
1.97
6x.268 = 1.61
6.8
.394
2.68
.039
.413
.138
.748
1.69
1.48
.984
.492
.453
.492 .492
.709
1.20
mounting thread M3
max. screw length 5.8 mm (.228 in.)
tightening torque max. 0.5 Nm
2 A
M1
2 A
M1
2
operating area
(reinforced insulation)
5
20
mounting area
(standard insulation)
.197
.787
11 1224123 2
Cut-out dimensions
16
32
24
ø11.5
12.5
12.5
3-pole
2-pole
1-pole
1.5
ø11.5
s
90°
recess with panel thickness
s > 1.5 mm (.059 in.)
36.6
.453
ø4
.157
.630
1.26
1.44
.945
.492
.492
.059
.453
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
Ordering information
Type No.
2210 single or multipole thermal-magnetic circuit breaker
Mounting
S socket or panel mounting
Actuator design
2 toggle
Number of poles
1 1-pole protected
2 2-pole protected
3 3-pole protected
Panel mounting
1 with M3 thread
Terminal design (main contacts)
P1 blade terminals 6.3-0.8 (QC .250)
Characteristic curve
F1
fast acting: therm.1.01-1.4xI
N
;magn.2-4xI
N
DC (DC only)
F2 fast acting: therm.1.01-1.4xI
N
;
magn.3.5-6.5xI
N
AC/ 4.5-8.5xI
N
DC
M1 standard delay: therm. 1.01-1.4xI
N
;
magn. 6-12xI
N
AC;7.8-15.6xI
N
DC
T1 delayed: therm. 1.01-1.4xI
N
; magn. 10-20xI
N
AC
M3 standard delay, low resistance: therm.1.4-1.8xI
N
;
magn. 6-12xI
N
AC; 7.8-15.6xI
N
DC
Intermediate position
H without intermediate position (standard)
Z with intermediate position
Auxiliary contacts
1 with auxiliary contacts in all poles
2 with auxiliary contacts in pole 1
(only multipole devices)
not suitable for Module 17plus
Auxiliary contact function (see diagram)
1 one each N/C and N/O (standard)
4 one N/C contact, closed in the
intermediate and ON position (-Z only)
Auxiliary contact - terminal design
1 same as main terminals
Current ratings
0.1...25 A
2210 - S 2 1 1 - P1 F1 - H 1 1 1 - 10 A ordering example
Approvals
Authority Standard Rated voltage Current ratings
VDE IEC/EN
60934
3 AC 433 V
AC 250 V
DC 65 V
0.1 A…32 A
0.1 A…32 A
0.1 A…32 A
UL UL 1077 AC 277/480 V
AC 277 V
DC 65 V
0.1 A…32 A
0.1 A…32 A
0.1 A…32 A
CSA C22.2 No
235
AC 277/480 V
AC 277 V
DC 65 V
0.1 A…32 A
0.1 A…32 A
0.1 A…32 A
CQC GB 17701 AC 250/433 V
AC 250 V
DC 65 V
0.1 A…25 A
0.1 A…25 A
0.1 A…25 A
GL IEC/EN
60934
3 AC 433 V
AC 250 V
DC 65 V
0.1 A…32 A
0.1 A…32 A
0.1 A…32 A
Thermal-Magnetic Circuit Breaker 2210-S2...
www.e-t-a.de
1646
3
1
Thermal-Magnetic Circuit Breaker 2210-S2...
Multipole devices: all poles symmetrically loaded. With single pole overload,
thermal tripping will be at max. 1.7 x I
N
with curves F1, F2 and M1 at max.
2.2 x I
N
with curve M3.
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section
Technical information.
Ambient °F
temp. °C
-22
-30
-4
-20
+14
-10
+32
0
+73.4
+23
+86
+30
+104
+40
+122
+50
+140
+60
Derating factor
0.76 0.79 0.83 0.88 1 1.04 1.11 1.19 1.29
Trip time in seconds
Trip time in seconds
Trip time in seconds
-F1 0.1…16 A DC only
0.001
124681020
40
10000
1000
100
10
1
0.1
0.01
6080100
-F2 8…16 A AC/ DC
1)
10000
0.001
0.001
1246810
20 40
1000
100
10
1
0.1
0.01
6080100
124681020
40
10000
1000
100
10
1
0.1
0.01
6080100
-F2 0.1…7.5 A AC/ DC
1)
-30 °C
-22 °F
+23 °C
+73.4 °F
+60 °C
+140 °F
… times rated current
… times rated current
… times rated current
1)
Magnetic tripping currents are increased by 30 % on DC supplies.
Internal connection diagrams Typical time/current characteristics
OFF position Intermediate position ON position
line line line
line line line
I
>
I
>
23
24
0 I
(Z)
111 23
12 24
2
0I
(Z)
11123
12 24
2
0I
(Z)
111
12
2
OFF position Intermediate position ON position
I
>
0I
(Z)
123
24
2
0I
(Z)
123
24
2
0
I
(Z)
123
24
2
I
>
I
>
I
>
with auxiliary contact function 1 (one each N/O and N/C)
(...-H111-...) without intermediate position
(...-Z111-...) with intermediate position
with auxiliary contact function 4 (1 N/O, leading)
Toggle positions
OFF position intermediate positionON position
Shock directions
56
4
3
1
2
current rating

2210-S221-P1T1-Z241-8A

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers 1077, 2P, PL, 277VAC/65VDC, T1, M3, 1NC AUX INT and ON, 8A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union