IB ST 24 DO16/3 Order No.: 2754914
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2754914
PHOENIX CONTACT Deutschland GmbH Page 2 / 6
http://www.phoenixcontact.de Feb 8, 2011
The scope of functions provided by the standard models covers the majority of applications. On top of this, several
modules provide additional electronic functions, such as:
- Output channels in up to four electrically isolated groups
- Separate electronic short-circuit protection for each output channel
- Higher output current, which are needed in individual applications.
All the typical advantages of INTERBUS-ST handling, such as multi-wire connection methods and plug-in electronics are
provided by both product lines.
Technical data
Interface
Fieldbus system Lokalbus
Name ST local bus
Type of connection ST local bus connector
Digital outputs
Output name Digital outputs
Type of connection Screw connection
Connection method 3-conductor
Number of outputs 16
Protective circuit Short-circuit protection Electronic
Maximum output current per channel 500 mA
Maximum output current per module / terminal
block
8 A
Maximum output current per group 2 A
Nominal load, inductive 12 VA (1.2 H; 48 Ω)
Nominal load, lamp 12 W (per output)
Nominal load, ohmic 12 W (per output)
Power supply for module electronics
Supply voltage 24 V DC
Supply voltage range 20 V DC ... 30 V DC (including ripple)
Ripple 3.6 V
pp
within the allowable voltage range
Current consumption 100 mA
Communications power U
L
9 V DC
Current consumption max. 100 mA